background image

Copley Controls, 20 Dan Road, Canton, MA 02021, USA 

Tel: 781-828-8090 

Fax: 781-828-6547 

Tech Support: E-mail: [email protected], Internet: http://www.copleycontrols.com 

Page 21 of 28

 

Xenus XTL

RoHS

Sin/Cos Encoder

Copley

Controls

Corp.

PIn

SIGnAL

PIn

SIGnAL

PIn

SIGnAL

1

Frame Gnd

6

Hall V

11

Encoder Cos(-)

2

+5 Vdc (note 1)

7

Encoder /X

12

Encoder Cos(+)

3

Hall U

8

Encoder X

13

Encoder Sin(-)

4

+5 Vdc (note 1)

9

Hall W

14

Encoder Sin(+)

5

Signal Gnd

10

[In5] Motemp

15

Signal Gnd

PIn

SIGnAL

PIn

SIGnAL

PIn

SIGnAL

1

Frame Gnd

10

[In6] HS

19

Signal Gnd

2

Ref(-)

11

[In7] HS

20

+5 Vdc (note 1)

3

Ref(+)

12

[In8] HS

21

Multi Encoder /X

4

[In1] Enable

13

[In9] HS

22

Multi Encoder X

5

[In2] GP

14

[In10] HS

23

Multi Encoder /B

6

[In3] GP

15

Signal Gnd

24

Multi Encoder B

7

[In4] GP

16

[OUT1]

25

Multi Encoder /A

8

[In11] GP

17

[OUT2]

26

Multi Encoder A

9

[In12] GP

18

[OUT3]

nOTES:

1. The total current drawn from the +5 Vdc outputs cannot exceed 400 mA

Pin

Signal

6

No connect

5

TxD Output

4

Ground

3

Ground

2

RxD Input

1

No connect

Pin

Signal

1

CAN_H

2

CAN_L

3

CAN_GND

4

No connection

5

No connection

6

(CAN_SHLD)

7

CAN_GND

8

(CAN_V+)

J8 MOTOR FEEDBACk

J7 COnTROL SIGnALS

J6 CAn BUS

J5 RS-232 (DTE)

ISOLATED CIRCUIT

notes:

1. CAn circuits are opto-isolated from drive circuits. 

2. CAn_GnD connects to drive Signal Ground. 

3. CAn_SHLD and CAn_V+ are wired-thru on both

 

J6 connectors and have no connection to the drive.

J5 CABLE COnnECTOR: 

  RJ-11 style, male, 6 position 

Cable:  6-conductor modular type

J6 CABLE COnnECTOR

:

RJ-45 style, male, 8 position 

Cable:   8-conductor modular type

J7 CABLE COnnECTOR: 

  High-Density D-Sub, 26 Position, Male

J8 CABLE COnnECTOR: 

  High-Density D-Sub, 15 Position, Male

Содержание Xenus R10 Series

Страница 1: ...pulse inputs reset digital torque or velocity reference or motor over temperature A twelfth input is dedicated to the drive Enable function Three programmable logic outputs are for reporting a drive...

Страница 2: ...74HC14 Schmitt trigger 100 ns RC filter Vin LO 1 35 Vdc Vin HI 3 65 Vdc 12 Vdc max Inputs IN7 10 Single ended Comparator with 2 5 Vdc reference 100 ns RC filter Vin LO 2 3 Vdc Vin HI 2 45 Vdc Differen...

Страница 3: ...motor cable shield feedback specifications GENERAL SPECIFICATIONS CONTINUED protections HV Overvoltage HV 400 Vdc Drive PWM outputs turn off until HV is less than overvoltage HV Undervoltage HV 60 Vd...

Страница 4: ...le transformation ratio Resolution 14 bits equivalent to a 4096 line quadrature encoder Reference frequency 7 5 kHz Reference voltage 2 8 Vrms auto adjustable by the drive to maximize feedback Referen...

Страница 5: ...1 DTE RxD 3 2 TxD 2 5 Gnd RxD TxD Gnd 5 3 RxD TxD 1 2 3 4 5 6 RJ 11 DTE RS 232 Xenus operates as a DTE device from a three wire full duplex RS 232 port at 9 600 to 115 200 Baud 8 bits no parity and on...

Страница 6: ...drive with a higher CAN node address For more information on CANopen communications download the CANopen Manual from the Copley web site http www copleycontrols com motion downloads pdf CANopenProgram...

Страница 7: ...e inputs or CANopen commands Green Slow Blinking Drive OK but NOT enabled Will run when enabled Green Fast Blinking Positive or Negative limit switch active Drive will only move in direction not inhib...

Страница 8: ...position commands can be in either single ended or differential format Single ended signals should be sourced from devices with active pull up and pull down to take advantage of the high speed inputs...

Страница 9: ...ed to the drive Enable function This is done to prevent accidental programming of the input in such a way that the controller could not shut it down Two types of RC filters are used GP general purpose...

Страница 10: ...nal diode in the output is for driving PLC inputs that are opto isolated and connected to 24 Vdc The diode prevents conduction from 24 Vdc through the 1 k resistor to 5 Vdc in the drive This could tur...

Страница 11: ...are less susceptible to noise that can degrade single ended outputs Encoder cables should use twisted pairs for each signal pair A A B B X X An overall shield should be used and for longer cables shie...

Страница 12: ...ly This is useful in systems that use external controllers that also need the motor feedback encoder signals because these now come from J7 the Control connector In addition to eliminating Y cabling w...

Страница 13: ...rame Ground 2 3 J2 U V W BRUSHLESS MOTOR Fuse Fuse 4 3 2 1 Mot U Mot V Mot W Frame Ground 3 L2 N 2 1 L1 L3 L2 L1 IN7 HS IN8 HS IN9 HS IN10 HS 10 IN1 Enable IN4 GP IN2 GP IN3 GP 3 Ref J7 10 Vdc Analog...

Страница 14: ...H 1 4 5 J3 REGEN REGEN Frame Ground 2 3 J2 U V W BRUSHLESS MOTOR Fuse Fuse 4 3 2 1 Mot U Mot V Mot W Frame Ground 3 L2 N 2 1 L1 L3 L2 L1 IN7 HS IN8 HS IN9 HS IN10 HS 10 IN1 Enable IN4 GP IN2 GP IN3 G...

Страница 15: ...3 J2 U V W BRUSHLESS MOTOR Fuse Fuse 4 3 2 1 Mot U Mot V Mot W Frame Ground 3 L2 N 2 1 L1 L3 L2 L1 11 IN7 HS 12 IN8 HS IN9 HS IN10 HS IN1 Enable IN4 GP IN2 GP IN3 GP 3 Ref J7 10 Vdc Analog Reference 1...

Страница 16: ...smaller wire gauge these should not be used as part of a safety ground system Motor cases can be safety grounded either at the motor by earthing the frame or by a grounding conductor in the motor cab...

Страница 17: ...e drive can radiate from the wire used for the safety ground connection In order to keep the path between the heatplate and earth as short as possible it s also recommended to mount the drive to the e...

Страница 18: ...0 V recommended for XTL 230 36 R and XTL 230 40 R models AWG 14 600V for XTL 230 18 R Shielded cable required for CE compliance J2 Cable Connector Wago 51118008 or 721 104 026 047 RN01 0000 Euro style...

Страница 19: ...OUT1 25 Multi Encoder A 8 IN11 GP 17 OUT2 26 Multi Encoder A 9 IN12 GP 18 OUT3 Pin Signal 6 No connect 5 TxD Output 4 Ground 3 Ground 2 RxD Input 1 No connect Pin Signal 1 CAN_H 2 CAN_L 3 CAN_GND 4 N...

Страница 20: ...V recommended for XTL 230 36 R and XTL 230 40 R models AWG 14 600V for XTL 230 18 R Shielded cable required for CE compliance J2 Cable Connector Wago 51118008 or 721 104 026 047 RN01 0000 Euro style...

Страница 21: ...Multi Encoder B 7 IN4 GP 16 OUT1 25 Multi Encoder A 8 IN11 GP 17 OUT2 26 Multi Encoder A 9 IN12 GP 18 OUT3 Notes 1 The total current drawn from the 5 Vdc outputs cannot exceed 400 mA Pin Signal 6 No c...

Страница 22: ...recommended for XTL 230 36 R and XTL 230 40 R models AWG 14 600V for XTL 230 18 R Shielded cable required for CE compliance J2 Cable Connector Wago 51118008 or 721 104 026 047 RN01 0000 Euro style 5 0...

Страница 23: ...P 15 Signal Gnd 24 Multi Encoder B 7 IN4 GP 16 OUT1 25 Multi Encoder A 8 IN11 GP 17 OUT2 26 Multi Encoder A 9 IN12 GP 18 OUT3 Notes 1 The total current drawn from the 5 Vdc output cannot exceed 400 mA...

Страница 24: ...r and Temperature Sensor Xenus operates as a CAN node All commands are passed on the CAN bus CME 2 is used for setup and configuration before installation as CAN node Serial Cable Kit SER CK Connects...

Страница 25: ...IVE for BRUSHLESS BRUSH MOTORS For multiple drive installations use the ordering guide on this page Computer equipment is the same as for single drive installations And Serial Cable Kit SER CK is used...

Страница 26: ...tion controller card Using the minimum requirements will allow CME 2 to run but the performance will be significantly reduced Xenus takes digital position commands in Pulse Direction or CW CCW format...

Страница 27: ...Line Filter Regen Resistor Optional Controller or PLC AC Mains 90 264 Vac 47 63 Hz 1 or 3 ph Copley Controls 20 Dan Road Canton MA 02021 USA Tel 781 828 8090 Fax 781 828 6547 Tech Support E mail sales...

Страница 28: ...rews There are two protective sheets blue on one side and clear on the other Both must be removed when the interface pad is installed STEPS TO INSTALL 1 Remove the blue protective sheet from one side...

Страница 29: ...heatsink and fan combinations enable operation at 55 C 1 2 3 3 M X M V M X M V M X M V Copley Controls 20 Dan Road Canton MA 02021 USA Tel 781 828 8090 Fax 781 828 6547 Tech Support E mail sales cople...

Страница 30: ...ermal material 4 Heatsink hardware Regeneration Resistors Optional XTL RA 03 Regeneration resistor assembly for XTL 230 18 30 W XTL RA 04 Regeneration resistor assembly for XTL 230 36 XTL 230 40 model...

Отзывы: