InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008
74
IL-NT-AMF-Reference Guide1.2.pdf
Communication object vs. Register
All the data intended for communication has its representation as communication objects in the
controller. The communication object is represented by the n-byte array in the controller memory and
identified by the unique 16-bit communication object number. The register, according to Modbus
communication protocol, represents a two-byte data and in communication functions is referenced by
16-bit register address. Further in the description of communication functions
the communication
object number will always be used as a register address
and length of the communication object
will be expressed by number of registers.
Just one communication object can be read or written
by one communication function.
Hint:
To obtain communication object numbers it is possible to download the actual controller description
on-line from controller or from (ail) archive and use “export data” function from LiteEdit software.
Communication object list (exported from default IL-NT-AMF25 archive)
Setpoints of AMF25:
Name Firmware
ver.
Application
Date
App.
ver.
Ser.
num.
Filename
IL-NT
IL-NT-1.2.1
R:13.03.2008 AMF25
13.3.2008 1,2 12345678
IL-NT-AMF25-
1.2.1.AIL
Group Name
Value
Dimension
Password
Com.
obj.
Low
limit
High
limit
Data type
Basic Settings
Gen-set Name
IL-NT
No
8637
Short string
Basic Settings
Nominal Power
200
kW
No
8276
1
32000
Unsigned 16
Basic Settings
Nomin Current
350
A
No
8275
1
10000
Unsigned 16
Basic Settings
CT Ratio
2000
/5A
No
8274
1
5000
Unsigned 16
Basic Settings
PT Ratio
1,0
/1
No
9579
0,1
500,0
Unsigned 16
Basic Settings
Vm PT Ratio
1,0
V/V
No
9580
0,1
500,0
Unsigned 16
Basic Settings
Nominal Volts
231
V
No
8277
80
20000
Unsigned 16
Basic Settings
Nominal Freq
50
Hz
No
8278
45
65
Unsigned 16
Basic Settings
Gear Teeth
120
No
8252
0
500
Unsigned 16
Basic Settings
Nominal RPM
1500
RPM
No
8253
100
4000
Unsigned 16
Basic Settings
ControllerMode
OFF
No
8315
String list
Basic Settings
FltResGoToMAN
DISABLED
No
9983
String list
Basic Settings
ControllerAddr
1
Yes
24537
1
32
Unsigned 8
Basic Settings
COM1 Mode
COMAP
Yes
24522
String list
Engine Params
Starting RPM
25
%
No
8254
5
50
Unsigned 8
Engine Params
Starting Oil P
4,5
Bar
No
9681
0,0
10,0
Integer 16
Engine Params
Prestart Time
2
s
No
8394
0
600
Unsigned 16
Engine Params
MaxCrank Time
5
s
No
8256
1
60
Unsigned 8
Engine Params
CrnkFail Pause
8
s
No
8257
5
60
Unsigned 8
Engine Params
Crank Attempts
3
No
8255
1
10
Unsigned 8
Engine Params
Idle Time
12
s
No
9097
0
600
Unsigned 16
Engine Params
Min Stab Time
2
s
No
8259
1
10
Unsigned 16
Engine Params
Max Stab Time
10
s
No
8313
2
300
Unsigned 16
Engine Params
Cooling Time
30
s
No
8258
0
3600
Unsigned 16
Engine Params
Stop Time
60
s
No
9815
0
240
Unsigned 16