InteliLite
NT
– AMF20/25, SW version 1.2, ©ComAp – March 2008
5
IL-NT-AMF-Reference Guide1.2.pdf
WARNING – VERY IMPORTANT !!!
Every time you want disconnect following InteliLite
NT
controller terminals:
•
Mains voltage measuring and / or
•
Binary output for MCB control and / or
•
MCB
Feedback
Switch InteliLite to MAN or OFF Mode or disconnect the Binary outputs Starter and
Fuel to avoid unexpected automatic start of gen-set and GCB closing
.
All parameters are preadjusted to their typical values. But the set points in the “
Basic settings
” settings
group
!!must!!
be adjusted before the first startup of the gen-set.
!!! WRONG ADJUSTMENT OF BASIC PARAMETERS
CAN DESTROY THE GEN-SET !!!
The following instructions are for qualified personnel only. To avoid personal injury do
not perform any action not specified in this User guide !!!
In no case touch the terminals for voltage and current measurement!
Always connect grounding terminals!
In any case do not disconnect InteliLite
NT
CT terminals !
Adjust set points
Dangerous voltage
!!! CAUTION !!!