Vm PT Ratio
[/1]
Mains potential transformers ratio.
Step:
0,1 V / V
Range:
0,1 – 500,0 V / V
Nomin
Voltage
[V]
Nominal generator voltage (phase to neutral)
Step:
1V
Range:
80 – 20000 V
Nominal
Freq
[Hz]
Nominal generator frequency (usually 50 or 60 Hz )
Step:
1Hz
Range:
45 – 65 Hz
Gear
Teeth
[-]
Number of teeth on the engine gear for the pick-up.
Set to zero, if no pick-up is used. Engine speed is counted from the generator frequency.
Step:
1
Range:
0 – 500
Hint:
Generator frequency can be used only when generator voltage (min 5V) is present before reaching of
the firing speed (
Starting RPM
) after start.
Nominal
RPM
[RPM]
Nominal engine speed.
Step:
1RPM
Range:
100 – 4000 RPM
ControllerMode
[ OFF, MAN, AUT,*TEST ]
Equivalent to Controller mode changes by MODE
→
or
←
MODE buttons.
Hint:
Controller Mode change can be separately password protected.
FltResGoToMAN
[ENABLED/DISABLED]
DISABLED:
Controller stays in AUT Mode after Fault Reset .
ENABLED:
Automatic switch from AUT (or TEST) to MAN Mode after Fault Reset to avoid
automatic engine start. This function is active for Shut down protection only.
ControllerAddr (1 .. 32)
[-]
Controller identification number. It is possible to set controller address different from the default value
(1) so that more IL controllers can be interconnected (via RS485) and accessed e.g. from Modbus
terminal.
Hint:
When opening connection to the controller it's address has to correspond with the setting in PC tool.
From LiteEdit it is only possible to connect to controllers with address 1.
COM1
Mode [STANDARD/MODBUS/CUMMINS]
Communication protocol switch.
COMAP:
LiteEdit communication protocol.
Modbus:
Modbus protocol.
CumminsMB: Protocol for communication with Cummins engines via Modbus.