
InteliDrive DCU Marine - 3.0.0 Global Guide
148
Setpoint group
RPMdep Protect
Related FW
3.0.0
Range [units]
0 .. 600 [s]
Default value
10
Step
1
Comm object
10151
Related applications
PRP
Config level
Standard
Setpoint visibility
Always
Description
RPM dependent Coolant pressure protection delay. Corresponding protection is activated when Coolant
pressure is below limit for CoolPrRPMdel.
To activate RPM dependent coolant pressure protection any analog value has to be linked with LAI: Coolant
Press.
Note:
RPM dependent coolant pressure protection is fix configured Protection block type = Engine
running only with RunOnlyBlkDel1 delay.
CoolPrRPMdel
Содержание InteliDrive DCU Marine
Страница 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Страница 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Страница 104: ...InteliDrive DCU Marine 3 0 0 Global Guide 104 8 Appendix 8 1 Controller objects 105 6 back to Table of contents ...
Страница 242: ...InteliDrive DCU Marine 3 0 0 Global Guide 242 Binary output to J1939 configuration Source Value 8 1 5 Analog Inputs ...
Страница 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Страница 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Страница 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...