
InteliDrive DCU Marine - 3.0.0 Global Guide
134
Engine protect
Setpoint group
Engine protect
Related FW
3.0.0
Range [units]
0 .. 600 [s]
Default value
10
Step
1
Comm object
8264
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
The maximum time for which is the binary output Horn closed (horn, buzzer will sound). If it is requested to
sound hound until alarm is cleared, set the parameter to zero.
Horn Timeout
Setpoint group
Engine protect
Related FW
3.0.0
Range [units]
0 .. 60 [s]
Default value
10
Step
1
Comm object
10023
Related applications
All
Config level
Standard
Setpoint visibility
Always
Description
This parameter adjusts delay after engine start when alarms configured as RunOnlyBlkDel1 (i.e. "running
only", group #1) are started to be evaluated. The "running only" alarms are not beeing evaluated while the
engine is not running or then, after start, while the adjusted delay is running.
For details see drawing, which is part of
description.
RunOnlyBlkDel1
Содержание InteliDrive DCU Marine
Страница 29: ...InteliDrive DCU Marine 3 0 0 Global Guide 29 Protection delay and blocking ...
Страница 51: ...InteliDrive DCU Marine 3 0 0 Global Guide 51 4 2 2 Electronic engine without redundancy line ...
Страница 104: ...InteliDrive DCU Marine 3 0 0 Global Guide 104 8 Appendix 8 1 Controller objects 105 6 back to Table of contents ...
Страница 242: ...InteliDrive DCU Marine 3 0 0 Global Guide 242 Binary output to J1939 configuration Source Value 8 1 5 Analog Inputs ...
Страница 255: ...InteliDrive DCU Marine 3 0 0 Global Guide 255 Analog inputs from J1939 configuration ...
Страница 265: ...InteliDrive DCU Marine 3 0 0 Global Guide 265 Engine Values ...
Страница 285: ...InteliDrive DCU Marine 3 0 0 Global Guide 285 6 back to Appendix 6 back to Table of contents ...