85
FieldSmart
®
Fiber Active Cabinet (FAC) 3200
__________________________________________________________
Installation Manual
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeClearfield.com • [email protected]
Manual 020421 REV A - Jan 2019
Step 1:
Step 2:
Step 3:
Step 4:
Installing Batteries
The FAC 3200 cabinet can house a single string of front-terminal VRLA batteries (four batteries per string). A cabinet
equipped with an optional riser compartment can support a second battery string. See
Supported Batteries
for a list of sup-
ported battery types.
WARNING!
Electrical hazard. Batteries contain a stored charge. Only a qualified technician should perform
this procedure.
CAUTION!
Electrical, chemical, fire, and heat hazard. Handle batteries with care to avoid personal injury or
damage to the equipment.
ALERT!
Read the battery manufacturer’s instructions before installing batteries. Follow the manufacturer
guidelines and local safety practices.
To prepare batteries for installation
Unpack the batteries from the shipping packaging.
Remove the terminal caps from the top of each battery.
Clean and apply No-Ox anti-corrosion grease to each battery terminal.
Locate the bagged kit containing the string jumper straps and other materials. Set the kit aside for use during
installation.
WARNING!
In -48V telecom systems, red leads connect to the negative terminal and black leads connect to
the positive terminal. Do not reverse the wiring polarities.