To install AC power (110-120 VAC)
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
Step 7:
Step 8:
Step 9:
Verify that all AC load center breakers are in the OFF position.
Remove the AC duct cover (two panels) as follows:
a.
Loosen (but do not remove) the mounting screws securing the duct cover panels to the fixture.
b.
Slide the upper panel sideways to align its two keyholes with the two mounting screws. When aligned, pull
the panel away from the fixture.
c.
Slide the lower panel sideways to align its two keyholes with the two mounting screws. When aligned, pull
the panel away from the fixture.
Pull the AC cable into the cabinet through the entry hole in the base of the compartment.
Route the AC cable up through the duct and feed it into a hole on the left side of the AC load center.
Remove the Main Service Disconnect breaker from the load center housing to ease wire termination. Pull the
breaker straight out to disengage it from the assembly.
Connect the AC wiring as follows:
• Connect the green (ground) lead to the ground bus bar.
• Connect the white (neutral) lead to the neutral bar.
• Connect the L1 lead to the left side of the Main Service Disconnect breaker.
Re-attach the Main Service Disconnect breaker into the load center.
Dress and secure the AC cable, providing adequate strain relief.
Replace the AC duct cover (two panels) and the left cover panel on the AC load center.