103
FieldSmart
®
Fiber Active Cabinet (FAC) 3200
__________________________________________________________
Installation Manual
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeClearfield.com • [email protected]
Manual 020421 REV A - Jan 2019
Step 3:
Route and terminate the single OLT-side fiber (red SC connector) from the PON splitter (identified as IN) to the
SC adapter plate.
Step 4:
IMPORTANT!
When routing optic fibers, be careful to avoid bending fibers beyond the manufacturer
recommended 1 inch (2.54 cm) bend radius. Exceeding the bend radius can cause excess attenuation and
possibly break the fiber.
Route and terminate the (16 or 32) PON-side fibers from the splitter to the fiber staging area as follows:
a.
Dress the fibers from the splitter to the right and through the dressing spools as desired, allowing adequate
slack.
b.
Route the fibers from the dressing spools to the left across the front of the bulkhead panel to the staging
area.