CIAS Elettronica S.r.l.
Ed 2.3
Installation manual
Page
47
of
79
IB-SYSTEM-R
The following figure shows the connections provided from the server on the system terminal
block.
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
1
6
1
8
2
0
1
7
1
9
SW2
sets the server address, set all to 0 (all ON) if you have only one server.
SW3
chooses the serial line termination type; follow the table below to set
SW3
dip switches.
SW3
Line termination settings
DIP1
DIP2
DIP3
DIP4
OFF
OFF
OFF
OFF
Serial line not terminated or polarized
ON
OFF
OFF
ON
Serial line polarized
OFF
ON
ON
OFF
Serial line terminated
ON
ON
ON
ON
Serial line terminated and polarized
SW4
sets the server operating mode.
SW4
Descrizione
DIP 1
Printer enable: set ON if there is a parallel printer connected.
DIP 2
Second rack enable: set ON if there are 2 racks.
DIP 3
Terminal enable: set ON if there is an installation serial terminal.
DIP 4
ACQ enable: set ON during installation process.
DIP 5
Set always OFF
DIP 6
Firmware update: enable firmware updating.
Warning
: firmware updating prevents normal operation of the server, during the installation
process be careful to switch SW4 DIP 6 OFF.
Front panel description:
Function
Description
TX
Lights when the server sends data over the sensor serial line.
RX
Lights when the server receives data from the sensor serial line.
FAULT
Lights when there is a fault in the power supply or battery backup.
POWER
Lights when the server is ON.