INST.No.INE-378-P9CE
- 30 -
[
Number of analog output
correction data number of knee-point]
6.5.8 Analog output correction programming
This mode is for the correction of the analog output by knee-points (up to 8 points).
It is necessary to program from 6.5.8-1 to 6.5.8-5 continuously.
6.5.8-1 Programming of number of analog output correction data
(number of knee-point)
Program the number of the knee-point. When “0” is programmed, no analog output correction is executed.
1) To program the number of the analog output correction data,
press
SEL
key in the engineering mode screen until “
CP.n
”
appears in the sub display as shown in the right figure.
2) By pressing
key, the least significant digit of the main
display will blink.
3) Use
△
or
▽
key to program the desired value.
4) To activate this programming, press
ENT
key.
6.5.8-2 Programming of analog output correction data No.
Program the analog output correction data No, for the data to be corrected.
1) After the programming of the number of the analog output
correction data (number of knee-point) in [6.5.8-1
Programming of number of analog output correction data
(number of knee-point)], press
SEL
key until “
no
”
(programming screen of analog output correction data No.)
appears in the sub display as shown in the right figure.
2) By pressing
key, the least significant digit of the main
display will blink.
3) Use
△
or
▽
key to program the desired value.
4) To activate this programming, press
ENT
key.
• The numeric figure in the main display is available from
0
to
9
.
However, the programmable range is
0
and
2
to
8
.
• The default value is
0
.
Remark s
• The numeric figure in the main display is available from
0
to
9
.
However, the programmable range is
1
to
8
.
• The default value is
1
.
R e m a r k s
Tb
CONT
MEM
PEAK
AL
AH
C
F
ε
[
Analog output
correction data No.]
Main display
Sub display
Tb
CONT
MEM
PEAK
AL
AH
C
F
ε
Main display
Sub display