INST.No.INE-378-P9CE
- 23 -
6.5.3 Hold functions (Hold disable, sample hold, peak hold) selection
This mode is for the selection of the hold function (hold function disable, sample hold or peak hold).
When the peak hold is selected, [6.5.3-2 Peak hold reset type (time reset or remote contact reset)
selection] is necessary. Furthermore, when the internal time reset is selected, [6.5.3-3 Peak hold reset time
programming] is necessary.
For the sample hold, only the selection of the hold mode is required.
6.5.3-1 Hold function type selection
1) To select the hold function type, press
SEL
key in the
engineering mode screen until “
HoLd
” appears in the sub
display as shown in the right figure.
2) By pressing
key, “
no
”, “
PEAk
” or “
SAMP
” will blink in
the main display.
3) Use
△
or
▽
key to select the desired type.
4) To activate this selection, press
ENT
key.
[Hold function types]
no
: Hold function
disable
PEAk
: Peak hold
SAMP
: Sample hold
• The default is no (hold function disable).
R e m a r k s
Tb
CONT
MEM
PEAK
AL
AH
C
F
ε
[Hold function disable]
Main display
Sub display
Caution
For the sample hold, the measured value is hold by the remote contact.
(The pulse width more than 55m/sec is required for the remote contact.)
[Sample hold]
〕
Tb
CONT
MEM
PEAK
AL
AH
C
F
ε
Main display
Sub display
[Peak hold]
Tb
CONT
MEM
PEAK
AL
AH
C
F
ε
Sub display
Main display
Input form
【
Sample hold
】
Output form
External
contact output