INST.No.INE-378-P9CE
- 22 -
6.5.2 Analog dummy output programming
This programming is for analog dummy output based on programmed ratio. The output of 0 to 100% is
corresponding to 4 to 20mA. Note that this screen will not move to the measurement mode even if any
key is not pushed for 1 minute.
1) To program the dummy analog output, press
SEL
key in the
engineering mode screen until “
OutC
” appears in the sub
display as shown in the right figure.
2) By pressing
key, the most significant digit of the main
display will blink.
3) Use
△
or
▽
key to program the desired value.
4) To shift to the next lower digit, press
key.
The next lower digit will blink.
5) Repeat the above procedure of (3) and (4) up to the least
significant digit for programming (4 digits).
6) To activate this programming, press
ENT
key.
Then, the programmed value is outputted as a dummy output.
• Programmable range is
0
to
100
(%).
Example)
0
(%) = 4mA,
50
(%) = 12mA,
100
(%) = 20mA
• The default value is
0
(%).
Re m ar k s
Tb
CONT
MEM
PEAK
AL
AH
C
F
ε
Main display
Sub display
Caution
When “
OutC
” is displayed, “
0
” is displayed in the main display. However, the
dummy output corresponding to “
0
” is not outputted even if
ENT
key is pressed on
this condition.
Take the above procedure to program to “
0
”. If the dummy output is not required,
press SEL key with “
0
” displayed to move to the next programming mode.