16.3 Status and Constants Description
16.3.1 Module status explanation (A1):
16.3.1.1 eStatusACOut:
Name
Description
Value
SBR
Standby running. This means that the module is delivering
output
0
SB
Standby. This mean that the module is manually OFF
1
SBWE
Standby with error. This means that the module is not
delivering output due to an unrecoverable error
2
SBWRE
Standby with recoverable error. This means that the module
is not delivering output due to a recoverable error.
3
UNKNOWN
Unknown. This means status is unknown
4
16.3.1.2 eStatusACIn:
Name
Description
Value
OK
OK. This means the AC input is OK for the module
0
SAFE
Safe. This means the AC input is not considered as “good”
but some power can still be drawn from it.
1
NOT_SYNC
Not synchronized. This means that the AC input and output
are not synchronized together thus invalidating AC input.
2
OFF
Off. This means that the AC input stage of the module has
been turned off due to an invalid AC input (maybe not safe).
3
UNKNOWN
Unknown. This means the status is unknown
4
16.3.1.3 eStatusDCIn:
Name
Description
Value
OK
OK. This means the AC input is OK for the module
0
FAIL
Fail. This means the DC input voltage is out of valid range.
1
UNKNOWN
Unknown. This means the status is unknown
2
16.3.2 Alarm types:
Name
Description
Value
NO_ALARM
Defines an event that is not considered as an alarm
0
MINOR
Defines an event that is to be considered as a minor alarm
1
MAJOR
Defines an event that is to be considered as a major alarm
2
84
– Monitoring T2S - ETH User Manual – v1.4