– Monitoring T2S - ETH User Manual – v1.4
Graphical User Interface
•
AC Out
Phase shift & Vout for each
phase
: define phase shift between
phase.
Nominal Freq
: nominal frequency
50 or 60 Hz.
Nb of phases
: Number of phase
single or three phase.
Short circuit voltage & hold time
:
short circuit hold time before shut
down 10 to 600 seconds (default
60).
Max power/current derating
.
Max overload duration
.
Saturation Threshold
: Saturation
level (default 80%) generate alarm
if AC output power exceed 80% of the total installed power.
Delta mode
: operation mode delta for 3 phase configuration only.
•
Synchronization
Synchronization parameters are
used to configure in the higher
capacity system (> 32 inverter
modules) by using TUS.
TUS is a synchronization kit.