![CE+T Power T2S-ETH Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/ce-t-power/t2s-eth/t2s-eth_user-manual_2577175079.webp)
16.2.3.1 INPUT REGISTERS ELEMENTS (Read-Only 16-bit wide)
Module table (0x0000)
The table described below represents the information that can be retrieved regarding a particular module. Maximum
amount of module is set to 32. Each of them is identified by an address ranging from 1 to 32.
BASE ADDRESS
: 0(0x0000) + 31*(Module address – 1).
Index
Name
Description
Type
0H
eStatusACOut
AC output status number (see 16.3.1.1, page 84)
U8
0L
eStatusACIn
AC input status number (see 16.3.1.2, page 84)
U8
1H
eStatusDCIn
DC Input status number (see 16.3.1.3, page 84)
U8
1L
bAddress
Configured address
U8
2H
bLoadPosition
Position of the load regarding input power sources (0:AC, 100:DC,
50:mixed, 101:unknown)
U8
2L
bLoadRatioW
Loading ratio regarding power in watts (%)
U8
3H
bLoadRatioVA
Loading ratio regarding power in VA (%)
U8
3L
bPhaseNumber
Number of the phase module is belonging to
U8
4
wVout
Output voltage value (0.1V)
U16
5
wIout
Output current value (0.1A)
U16
6
wPoutW
Output power value (W)
U16
7
wPoutVA
Output power value (VA)
U16
8
wVinAC
AC input voltage value (0.1V)
U16
9
wIinAC
AC input current value (0.1A)
U16
10
wPinACW
AC input power value (W)
U16
11
wPinACVA
AC input power value (VA)
U16
12
wACInFreq
AC input frequency value (0.1Hz)
U16
13
wVinDC
DC input voltage value (0.1V)
U16
14
wIinDC
DC input current value (0.1A)
U16
15
wPinDC
DC input power value (W)
U16
16
wTemperature
Temperature value (K)
U16
17
wSoftVersion
Software version number
U16
18
lSerialNumber
Serial number
U32
22H
bStatusMod
Event number of the status related to the output stage and the module
internal status
U8
22L
bStatusAC
Event number of the status related to the AC input stage
U8
23H
bStatusDC
Event number of the status related to the DC input stage
U8
23L
bPresent
Flag (true or false) that indicates if module is seen by T2S ETH or not
U8
24H
bGroupAC
AC input group number module is belonging to
U8
24L
bGroupDC
DC input group number module is belonging to
U8
25H
bRestrained
Flag (true or false)that indicates if module cannot cope with more than
five other module or not
U8
79
– Monitoring T2S - ETH User Manual – v1.4
Annex 3: Modbus
Содержание T2S-ETH
Страница 64: ...64 Monitoring T2S ETH User Manual v1 4 SNMP...
Страница 96: ......