![CE+T Power T2S-ETH Скачать руководство пользователя страница 81](http://html1.mh-extra.com/html/ce-t-power/t2s-eth/t2s-eth_user-manual_2577175081.webp)
Index
Name
Description
Type
26H
bNbInvNT
Number of modules not seen by T2S ETH in the phase (accordingly to
bNbOndCfg)
U8
AC group table (0x0730)
The table described below represents the information that can be retrieved regarding a particular AC group. Maximum
amount of AC group is set to 4. Each of them is identified by a label ranging from 1 to 4.
BASE ADDRESS
: 1840(0x0730) + 10*(AC group label – 1).
Index
Name
Description
Type
0H
bNbInvOK
Number of modules that are delivering output in the group
U8
0L
bNbInvMO
Number of modules manually off in the group
U8
1H
bNbInvKO
Number of modules that are not delivering output due to a failure in
the group
U8
1L
bNbInvSeen
Number of module seen by T2S ETH in that group
U8
2
lPinACW
AC input power value (W)
U32
4
lPinACVA
AC input power value (VA)
U32
6
wVinAC
AC input voltage value (0.1V)
U16
7
wIinAC
AC input current value (0.1A)
U16
8
wACInFreq
AC input frequency value (0.1Hz)
U16
9H
bACInOk
Number of modules stating that their AC input stage is fully functional
U8
DC group table (0x076C)
The table described below represents the information that can be retrieved regarding a particular DC group. Maximum
amount of DC group is set to 8. Each of them is identified by a label ranging from 1 to 8.
BASE ADDRESS
: 1900(0x076C) + 7*(DC group label – 1).
Index
Name
Description
Type
0H
bNbInvOK
Number of modules that are delivering output in the group
U8
0L
bNbInvMO
Number of modules manually off in the group
U8
1H
bNbInvKO
Number of modules that are not delivering output due to a failure in the
group
U8
1L
bNbInvSeen
Number of module seen by T2S ETH in that group
U8
2
lPinDC
DC input power value (W)
U32
4
wVinDC
DC input voltage value (0.1V)
U16
5
wIinDC
DC input current value (0.1A)
U16
6H
bDCInOk
Number of modules stating that their DC input stage is fully functional
U8
81