![CE+T Power T2S-ETH Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/ce-t-power/t2s-eth/t2s-eth_user-manual_2577175039.webp)
39
– Monitoring T2S - ETH User Manual – v1.4
Catena
8. Catena
8.1 Introduction
Catena is the display solution for T2S ETH. Using it, you get access on a 7’’ display directly in the system, providing the
same graphical user interface as the T2S ETH when accessed remotely.
8.2 User interface
As described before, the user interface is the same if the system is accessed remotely or directly on the 7’’ display.
The only limitation is the relay testing button, which is not available in Catena.
8.3 Ethernet connections
Catena has 3 ETH connections, two at rear and one at front.
8.3.1 Rear connections
One is dedicated to connection with T2S ETH while the second one is for permanent network connection. On this one,
Catena offers extra protocols: SNMP v2c, v3 and Modbus over TCPIP. See following section “Protocols” about these.
8.3.2 Front connection
The front ETH connection is the maintenance access of the Catena. As it’s providing a DHCP server, it’s not needed
anymore to change your laptop settings to connect point to point on the device.
When plugging an RJ45 cable between Catena and your laptop, the following popup will be displayed:
To get access to the user interface, just follow instruction from the popup:
•
Open a web browser (Chrome or Firefox)
•
Type http://catena.local in the address bar
When the cable is unplugged, the display is accessible again.
Important remark: this feature is only available in latest version (both Hardware and Software).