![CE+T Power T2S-ETH Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/ce-t-power/t2s-eth/t2s-eth_user-manual_2577175036.webp)
36
– Monitoring T2S - ETH User Manual – v1.4
Graphical User Interface
7.4.10.5 Power
•
General
Redundancy
: number of redundant
module can be set for each output
phase.
Source power ratio DC vs AC
:
percentage of power fed by DC. By
default this parameter is set to 0,
100% on AC input.
Booster 10x Iin
: enable the boost
(see manual of power module used
for information on this feature).
AC In grid feed Disable
: enable
this option if no power should be
fed from the AC Input.
•
AC In
Threshold values for module
operation on AC input side. User
shall modify it ONLY if he has
followed a proper training by
CE+T.
•
DC Group
User can configure the DC input
as per the number of battery bank
installed.
Maximum two DC groups can be
configured.