![CE+T Power T2S-ETH Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/ce-t-power/t2s-eth/t2s-eth_user-manual_2577175043.webp)
43
– Monitoring T2S - ETH User Manual – v1.4
Catena
Address
Description
Unit
Type
2104
Phase 2 voltage
V/10
S32/float
2106
Phase 2 current
A/10
S32/float
2108
Phase 2 frequency
Hz/100
S32/float
2110
Reserved
2112
Phase 2 worse power factor
%
S32/float
2114
Phase 2 worse temperature
°C/10
S32/float
2116
Phase 2 load ratio (W)
%
S32/float
2118
Phase 2 load ratio (VA)
%
S32/float
2120
Phase 2 available true power
W
S32/float
2122
Phase 2 available apparent power
VA
S32/float
Output phase 3
2150
Phase 3 true power
W
S32/float
2152
Phase 3 apparent power
VA
S32/float
2154
Phase 3 voltage
V/10
S32/float
2156
Phase 3 current
A/10
S32/float
2158
Phase 3 frequency
Hz/100
S32/float
2160
Reserved
2162
Phase 3 worse power factor
%
S32/float
2164
Phase 3 worse temperature
°C/10
S32/float
2166
Phase 3 load ratio (W)
%
S32/float
2168
Phase 3 load ratio (VA)
%
S32/float
2170
Phase 3 available true power
W
S32/float
2172
Phase 3 available apparent power
VA
S32/float
Input Group 1 Phase 1
Reserved
Phase true power
W
S32
Reserved
Phase apparent power
VA
S32
Reserved
Phase voltage
V/10
S32
Reserved
Phase current
A/10
S32
Reserved
Phase frequency
Hz/100
S32
Input Group 1 Phase 2
Reserved
Phase true power
W
S32
Reserved
Phase apparent power
VA
S32
Reserved
Phase voltage
V/10
S32
Reserved
Phase current
A/10
S32
Reserved
Phase frequency
Hz/100
S32
Input Group 1 Phase 3
Reserved
Phase true power
W
S32
Reserved
Phase apparent power
VA
S32
Содержание T2S-ETH