Index
Name
Description
Type
4L
bDaylightSaving
Flag (true or false) that specify if daylight saving is enable or not
U8
5
wYear
Year number
U16
Alarm table (0x07DA)
The table described below represents the information that can be retrieved regarding alarms. Maximum amount of
entries is set to 50. A valid entry represents an alarm present in the system. An invalid entry is an entry where all bits
of each field are set. All entries following an invalid entry will be invalid.
BASE ADDRESS
: 2010(0x07DA) + 2*(Entry number – 1)
Index
Name
Description
Type
0H
bDeviceNumber
Identifier that specifies which device is responsible of this alarm
(see 16.3.1, page 84)
U8
0L
bEventType
Type of the alarm (Major or minor) (see 16.3.1, page 84)
U8
1
wEventNumber
Alarm number identifier
U16
Rem
: See alarm types in the annexes for
bEventType description.
Configuration table (0x1040)
The table described below represents the information that can be retrieved regarding parameters that can be
configured in the T2S ETH controller. Maximum amount of entries is set to 500. Not all entries are valid. An invalid entry
is an entry where all bits of each field are set. Invalid entries might be interleaved with valid entries.
BASE ADDRESS
: 4160(0x1040) + 20*(Entry number – 1)
Index
Name
Description
Type
0
swParameter
Configured value of the parameter
S16
1
wValidity
Value indicating if last configured parameter value is valid
(see 16.3.4, page 85)
U16
2
wIdentifier
Unique value identifying the parameter
U16
3
wUnit
Value indicating in which units the parameter is expressed
(see 16.3.4, page 85)
U16
4
strParamDescription
Textual description of the parameter
32*U8
Event string table (0x4114)
The table described below represents the information that can be retrieved regarding event textual description.
Maximum amount of entries is set to 300. Each event is identified by an unique number (Event 0 exists!).
BASE ADDRESS
: 16660(0x4114) + 8*Event number
Index
Name
Description
Type
0
strEventTxt
Textual description of event
16*U8
83