Table 29 — Main Base Board (MBB) Connections
DISPLAY NAME
POINT DESCRIPTION
SENSOR LOCATION
TYPE OF I/O
CONNECTION PIN
NUMBER
INPUTS
Input power from TRAN2
control box
24 VAC
J1, 1-3
IGC.F
IGC Fan Request
gas section
switch input
J6, 4
FDWN
Fire shutdown switch
supply/return/space
switch input
J6, 6
G
Thermostat G (Fan)
space
switch input
J7, 2
W2
Thermostat W2 (2nd Stage Heat)
space
switch input
J7, 4
W1
Thermostat W1 (1st Stage Heat)
space
switch input
J7, 6
Y2
Thermostat Y2 (2nd Stage Cool)
space
switch input
J7, 8
Y1
Thermostat Y1 (1st Stage Cool)
space
switch input
J7, 10
FIL.S
Filter status switch
indoor fan section
switch input
J9, 2-3
HUM
Humidistat switch input
space
switch input
J9, 5-6
Not Used
0-5vdc digital input
J9, 7-9
Not Used
0-5vdc digital input
J9, 10-12
SPT
Space temperature (T55/56)
space
10k thermistor
J8, 1-2
SPTO
Space temperature offset (T56)
space
10k thermistor
J8, 2-3
OAT
Outdoor air temperature
outdoor coil support
10k thermistor
J8, 5-6
SAT
Supply air temperature
indoor fan housing, or
supply duct
10k thermistor
J8, 7-8
SCT.A
Saturated condenser temperature,
circuit A
outdoor coil, circuit A
5k thermistor
J8, 9-10
SCT.B
Saturated condenser temperature,
circuit B
outdoor coil, circuit B
5k thermistor
J8, 11-12
RAT Return Air
Temperature
Return
10k thermistor
J8, 13-14
FAN.S Fan status
switch
indoor fan section
switch input
J8, 15-16
SSP.A
Suction pressure, circuit A
compressor A suction pipe
0-5 VDC pressure
transducer
J8, 18-20
SSP.B
Suction pressure, circuit B
compressor B suction pipe
0-5 VDC pressure
transducer
J8, 21-23
Not Used
0-5 VDC
J8, 24-26
OUTPUTS
CRC
Cooling Reheat Control
relay
J10, 3
RH2.A
Reheat 2 Valve Circuit A
relay
J10, 6
RH2.B
Reheat 2 Valve circuit B
relay
J10, 9
IDF.1
Indoor fan relay 1
relay
J10, 11
IDF.2
Indoor Fan relay 2
relay
J10, 13
IDF.3
Indoor Fan relay 3
relay
J10, 16
ALRM
Alarm relay
relay
J10, 19
COMP.B
Compressor B1 relay
relay
J10, 21
COMP.A
Compressor A1 relay
relay
J10, 23
HT.1
Heat Stage 2 relay
relay
J10, 25
HT.2
Heat Stage 1 relay
relay
J10, 27
COMMUNICATION
Local Equipment Network (LEN)
communication
J5, 1-3
Carrier Comfort Network (CCN)
communication
J5, 5-7
Network device power
24 VAC
J5, 9-10
Scrolling Marquee Display (LEN)
communication
J4, 1-3
Scrolling Marquee Display power
24 VAC
J4, 5-6
Expansion LEN Bus
communication
J3, 1-3
Optional ECB power
24 VAC
J2, 1-2
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......