132
ECON
Economizer Configuration
ECON_CFG
DF.DB
Diff Dry Bulb Control
0=Disable
1=RAT - 0°F
2=RAT - 2°F
3=RAT - 4°F
4=RAT - 6°F
0=Disable DIFFBULB
UEFC
Unoccupied Free Cooling
0=Disabled
1=Unoccpied
2=PreOccupancy
2 UEFC_CFG
FC.TM
Free Cool PreOcc Time
1 to 9999
mins
120
UEFCTIME
FC.LO
Free Cool Low Temp Limit
-30 to 70
°F
50
OATLUEFC
PE.EN
Power Exhaust Installed
No/Yes
No: no FIOP
Yes: FIOP
PE_ENABL
PE.1
PE Stage1 Econo Position
0 to 100
%
40
PE1_POS
PE.2 PE
Stage2 Econo Position
0 to 100
%
75
PE2_POS
PE1C
Power Exhaust Stage1 CFM
0 to 15000
CFM
800 (04- 07)
1600 (08- 14)
3200 (17- 28)
PE1_CFM
PE2C
Power Exhaust Stage2 CFM
0 to 15000
CFM
0
PE2_CFM
IDF.C
Indoor Fan Max Speed CFM
500 to 15000
CFM
2000 (04- 07)
4000 (08-14)
8000 (17-28)
IDF_CFM
EN.SW
Enthalpy Switch
0=No Switch
1=Normal Open
2=Normal Closed
0: no FIOP
1: FIOP
ENTHLCFG
E.TRV
Economizer Travel Time
5 to 300
secs
150
ECONOTRV
E.MXB
Bottom Stage Max Econo
0 to 100
%
50
ECONMAXB
E.MXT
Top Stage Max Econo
0 to 100
%
25 (03-14)
0 (17- 28)
ECONMAXT
LOG.F
Log Title 24 Faults
No/Yes
T24LOGFL
EC.MD
T24 Econ Move Detect
1 to 10
T24ECMDB
EC.ST
T24 Econ Move SAT Test
10 to 20 T
24ECSTS
S.CHG
T24 Econ Move SAT Change 0 to 5
T24SATMD
E.SOD
T24 Econ RAT-OAT Diff
5 to 20
T24RATDF
E.CHD
T24 Heat/Cool End Delay
0 to 60
T24CHDLY
ET.MN
T24 Test Minimum Pos.
0 to 50
T24TSTMN
ET.MX
T24 Test Maximum Pos.
50 to 100
T24TSTMX
AIR.Q
Air Quality Config.
IAQ_CFG
IA.CF
IAQ Analog Input Config
0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0: no FIOP
1: FIOP
IAQANCFG
IA.FN
IAQ Analog Fan Config
0=Never
1=Occupied
2=Always
0 IAQANFAN
II.CF
IAQ Switch Input Config
0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0
IAQINCFG
II.FN
IAQ Switch Fan Config
0=Never
1=Occupied
2=Always
0 IAQINFAN
AQ.MN
Econo Min IAQ Position
0 to 100
%
10
0: FIOP EnergyX
IAQMINP
OVR.P
IAQ Override Position
0 to 100
%
100
IAQOVPOS
OA.CF
OAQ Analog Input Config
0=No OAQ
1=DCV
2=Lockout OAQ
0 OAQANCFG
OAQ.L
OAQ Lockout Limit
0 to 5000
600
OAQLOCK
AQD.L
AQ Differential Low
0 to 5000
100
DAQ_LOW
AQD.H
AQ Differential High
0 to 5000
700
DAQ_HIGH
DF.ON
Fan On AQ Differential
0 to 5000
600
DAQFNON
DF.OF
Fan Off AQ Differential
0 to 5000
200
DAQFNOFF
I.4M
IAQ Sensor Value at 4mA
0 to 5000
0
IAQ_4MA
I.20M
IAQ Sensor Value at 20mA
0 to 5000
2000
IAQ_20MA
O.4M
OAQ Sensor Value at 4mA
0 to 5000
0
OAQ_4MA
O.20M
OAQ Sensor Value at 20mA
0 to 5000
2000
OAQ_20MA
APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
Table X — Mode — Configuration (cont)
ITEM EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
Sub- TABLE
CCN POINT
ENTRY
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......