47
T111
Circuit B Loss of Charge
Lockout Circuit B
Manual
Low refrigerant or faulty suction pressure transducer
Service Test — Circuit B Loss of
Charge
T126
Circuit A High Discharge Pressure
Shutdown Circuit A
Automatic
An overcharged system, high outdoor ambient
temperature coupled with dirty outdoor coil, plugged
filter drier, or a faulty high-pressure switch.
Service Test — Circuit A High
Discharge Pressure
T127
Circuit B High Discharge Pressure
Shutdown Circuit B
Automatic
An overcharged system, high outdoor ambient
temperature coupled with dirty outdoor coil, plugged
filter drier, or a faulty high-pressure switch.
Service Test — Circuit B High
Discharge Pressure
T133
Circuit A Low Refrigerant Pressure
Add Strike for Circuit A
Automatic
Low refrigerant charge, dirty filters, evaporator fan
turning backwards, loose or broken fan belt, plugged
filter drier, faulty transducer, excessively cold return air,
or stuck open economizer when the ambient
temperature is low.
Service Test — Circuit A Low
Refrigerant Pressure
T134
Circuit B Low Refrigerant Pressure
Add Strike for Circuit B
Automatic
Low refrigerant charge, dirty filters, evaporator fan
turning backwards, loose or broken fan belt, plugged
filter drier, faulty transducer, excessively cold return air,
or stuck open economizer when the ambient
temperature is low.
Service Test — Circuit B Low
Refrigerant Pressure
T143
Circuit A Failure To Pressurize
Add Strike for Circuit A
Automatic Wiring causing reverse rotation or faulty compressor
Service Test — Circuit A Failure to
Pressurize
T144
Circuit B Failure To Pressurize
Add Strike for Circuit B
Automatic Wiring causing reverse rotation or faulty compressor
Service Test — Circuit B Failure to
Pressurize
T153
Real Timeclock Hardware Failure
No time and date schedule
operation
Automatic No time/date configured, software failure, or MBB
failure
A154
Serial EEPROM Hardware Failure
Unit Shutdown
Automatic Software failure or MBB failure
T155
Serial EEPROM Storage Failure
Error
Unit operation errors
Automatic Software failure or MBB failure
A156
Critical Serial EEPROM Storage Fail
Error
Unit Shutdown
Automatic Software failure or MBB failure
A157
A/D Hardware Failure
Unit Shutdown
Automatic Software failure or MBB failure
A163
Circuit A Down Due to Failure
Lockout Circuit A
Manual Circuit has 3 strikes or has been locked out by another
alarm
Service Test — Circuit A Down Due
to Failure
A164
Circuit B Down Due to Failure
Lockout Circuit B
Manual Circuit has 3 strikes or has been locked out by another
alarm
Service Test — Circuit B Down Due
to Failure
T173
Loss of communication with the
Energy Management Module
No action
Automatic MBB Software failure, reload software or replace board
T175
Loss of communication with VFD
Unit Shutdown
Automatic Communication connection bad or miswired,
misconfigured VFD.
T179
Loss of communication with the
Economizer Control Board
No economizer operation
Automatic Communication wiring problem with ECB or faulty MBB
or ECB
T180
Loss of communication with the
Economizer Actuator
No economizer operation
Automatic Communication wiring problem with actuator.
T181
Loss of communication with Outside
Air Unit
Reset OAU data
Automatic Wiring Problem or OAU communication failure
A200
Linkage Timeout Error — Comm
Failure
No Linkage Operation fall back
to local SPT
Automatic Received a table write from Linkage before, now not
receiving any linkage commands
A404
Fire Shutdown
Unit Shutdown
Automatic Smoke detected by smoke detector
T408
Dirty Air Filter
Alert Generated
Automatic Dirty Filter
T409
Fan Status Switch ON, fan
commanded off
If IDF.F = Yes, then Unit
Shutdown
If IDF.F =
YES, then
Manual,
otherwise
automatic
Bad Fan Status Switch. Configuration incorrect.
Fan Status Switch OFF, fan
commanded on
If IDF.F = Yes, then Unit
Shutdown
If IDF.F =
YES, then
Manual,
otherwise
automatic
Tripped Circuit Breaker. Broken belt. Bad indoor fan
motor. Configuration incorrect. Bad fan status switch.
T410
R-W1 Jumper Not Installed in Space
Temp Mode
Unable to run heat
Automatic Missing jumper wire
R-W1 Jumper Must Be Installed to
Run Heat In Service Test
Unable to Test Heat Outputs
Automatic Missing jumper wire
T411
Thermostat Y2 Input Activated
without Y1 Activated
Run unit as if Y2 and Y1 are
On
Automatic Bad Thermostat or Thermostat Wiring
Table 14 —
Comfort
Link Alarm Codes (cont)
ALARM
OR
ALERT
NUMBER
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET
METHOD
PROBABLE CAUSE
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......