118
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table K — Mode — Operating Modes (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/Sub-
TABLE
CCN POINT
CCN WRITE
STATUS
DISPLAY
WRITE
STATUS
OAU
Outside Air Unit Diagnostic
OAU_DIAG
OA.RN
OAU System Run State
1=AUTO
2=OFF
3=TEST
OAU_RUN
OA.OP
OAU Operating Mode
0=Off
1=ERV (DCV)
2=Free Cooling
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3
OAU_MODE
2P.DM
OAU 2- position Damper
Close/Open
OAUDMPR
WHL
OAU Wheel Speed
xxx
%
OAUWHEEL
LAT
OAU Leaving Air Temp
xxx.x
°F
OAU_LAT
EXAT
OAU Exhaust Air Temp
xxx.x
°F
OAU_EXAT
OA.MN
Minimum Outside Air CFM
xxxxx
CFM
MINOACFM
DCV.M
Min DCV Outside Air CFM
xxxxx
CFM
MINDCVSP
OA.FS
OAU OA Fan Speed
xxx
%
OAFANSPD
A.OA
Actual Outside Air CFM
xxxxx
CFM
ACTOACFM
C.OA
Command Outside Air CFM
xxxxx
CFM
CMDOACFM
PE.OF
Power Exhaust CFM Offset
xxxxx
CFM
EXOFFSET
EX.FS
OAU Exhaust Fan Speed
xxx
%
OAUPESPD
A.EX
Actual Exhaust Air CFM xxxxx
CFM
ACTEXCFM
C.EX
Command Exhaust Air CFM xxxxx
CFM
CMDEXCFM
BP.SP
Building Pressure Setpnt
x.xx
in H2O
OAU_BPSP
BP
Building Pressure
x.xx
in H2O
OAU_BP
TM.LO
OA Tempring Lockout Temp xx
°F
OATMPLOC
TM.SP
OA Tempring SAT Setpoint
xx
°F
OATMPSPT
OA.HT
OAU Tempering Heater
xxx
%
OAHEATER
ALM.1
OAU Motor Failure Alarm
Off/On
OAUALRM1
ALM.2
OAU Dirty Filter Alarm
Off/On
OAUALRM2
ALM.3
OA Low CFM Alarm
Off/On
OAUALRM3
ALM.4
OAU Alarm
Off/On
OAUALRM4
DMD.L
DEMAND LIMITING
DMDL
D.LMT
Demand Limit In Effect
No/Yes
MODEDMDL
LMT.C
Max Cool Stage In Effect
x
CSTGLIMT
LMT.H
Max Heat Stage In Effect
x
HSTGLIMT
REDL
Redline Activated
No/Yes
MODEREDL
SHED
Loadshed Activated
No/Yes
MODESHED
MAX.C
Max Allowed Cool Stages
x
MAXCSTGS
MAX.H
Max Allowed Heat Stages
x
MAXHSTGS
(Display TRIM
- see
Configuration)
Sensor Calibration
TRIM
Space Temp Calibration
-30 to 130
°F
SPT_CAL
forcible
Space Temp Trim
-30 to 30
^F
SPT_OFF
forcible
Supply Air Temp Calib.
-30 to 130
°F
SAT_CAL
forcible
Supply Air Temp Trim
-30 to 30
^F
SAT_OFF
forcible
Return Air Temp Calib.
-30 to 130
°F
RAT_CAL
forcible
Return Air Temp Trim
-30 to 30
^F
RAT_OFF
forcible
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......