104
OAU
Outside Air Unit Status
OAUDISP
OA.RN
OAU System Run State
1=AUTO
2=OFF
3=TEST
OAU_RUN
OA.OP
OAU Operating Mode
0=Off
1=ERV (DCV)
2=Free Cooling
3=OA Tempering
4=Defrost
5=Test
6=Ext. Mode 1
7=Ext. Mode 2
8=Ext. Mode 3
OAU_MODE
UPC
UPC Software Version
xxxx
UPC_VER
OAU
OA Unit Software Version
xxxx
OAU_VER
2P.DM
OAU 2-position Damper
Close/Open
OAUDMPR
WHL
OAU Wheel Speed
xxx
%
OAUWHEEL
LAT
OAU Leaving Air Temp
xxx.x
°F
OAU_LAT
EXAT
OAU Exhaust Air Temp
xxx.x
°F
OAU_EXAT
OA.MN
Minimum Outside Air CFM
xxxxx
CFM
MINOACFM
DCV.M
Min DCV Outside Air CFM
xxxxx
CFM
MINDCVSP
OA.FS
OAU OA Fan Speed
xxx
%
OAFANSPD
A.OA
Actual Outside Air CFM
xxxxx
CFM
ACTOACFM
C.OA
Command Outside Air CFM
xxxxx
CFM
CMDOACFM
PE.OF
Power Exhaust CFM Offset xxxxx
CFM
EXOFFSET
EX.FS
OAU Exhaust Fan Speed
xxx
%
OAUPESPD
A.EX
Actual Exhaust Air CFM xxxxx
CFM
ACTEXCFM
C.EX
Command Exhaust Air CFM xxxxx CFM
CMDEXCFM
BP.SP
Building Pressure Setpnt
x.xx
in H2O
OAU_BPSP
BP
Building Pressure
x.xx
in H2O
OAU_BP
TM.LO
OA Tempring Lockout Temp xx
°F
OATMPLOC
TM.SP
OA Tempring SAT Setpoint
xx
°F
OATMPSPT
OA.HT
OAU Tempering Heater
xxx
%
OAHEATER
HRS
Component Run Hours
STRTHOUR
A1
Compressor A1 Run Hours
xxxxx.xx
hours
HR_A1
forcible
B1
Compressor B1 Run Hours
xxxxx.xx
hours
HR_B1
forcible
IDF1
Indoor Fan 1 Run Hours
xxxxx.xx
hours
HR_IDF1
forcible
IDF2
Indoor Fan 2 Run Hours
xxxxx.xx
hours
HR_IDF2
forcible
IDF3
Indoor Fan 3 Run Hours
xxxxx.xx
hours
HR_IDF3
forcible
HT.1
Heat Stage 1 Run Hours
xxxxx.xx
hours
HR_HTR_1
forcible
HT.2
Heat Stage 2 Run Hours
xxxxx.xx
hours
HR_HTR_2
forcible
PE.1
Power Exhaust1 Run Hours
xxxxx.xx hours
HR_PE_1
forcible
PE.2
Power Exhaust2 Run Hours
xxxxx.xx hours
HR_PE_2
forcible
ALRM
Alarm Relay Run Hours
xxxxx.xx hours
HR_ALM
forcible
CRC
Reheat1 Valve Run Hours
xxxxx.xx hours
HR_CRC
forcible
RH2.A
Reheat2 Valve A Run Hrs
xxxxx.xx hours
HR_RH2_A
forcible
RH2.B
Reheat2 Valve B Run Hrs
xxxxx.xx hours
HR_RH2_B
forcible
STRT
Component Starts
A1
Compressor A1 Starts xxxxxx
ST_A1
forcible
B1
Compressor B1 Starts xxxxxx
ST_B1
forcible
IDF1
Indoor Fan 1 Starts
xxxxxx ST_IDF1
forcible
IDF2
Indoor Fan 2 Starts
xxxxx.xx ST_IDF2
forcible
IDF3
Indoor Fan 3 Starts
xxxxx.xx ST_IDF3
forcible
HT.1
Heat Stage 1 Starts
xxxxxx
ST_HTR_1
forcible
HT.2
Heat Stage 2 Starts
xxxxxx
ST_HTR_2
forcible
PE.1
Power Exhaust 1 Starts
xxxxxx
ST_PE_1
forcible
PE.2
Power Exhaust 2 Starts
xxxxxx
ST_PE_2
forcible
ALRM
Alarm Relay Starts
xxxxxx
ST_ALM
forcible
CRC
Reheat1 Valve Starts
xxxxxx ST_CRC
forcible
RH2.A
Reheat2 Valve A Starts
xxxxxx ST_RH2_A
forcible
RH2.B
Reheat2 Valve B Starts
xxxxxx ST_RH2_B
forcible
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table A — Mode — Run Status (cont)
ITEM EXPANSION
RANGE
UNITS
CCN TABLE/
SUB-TABLE
CCN POINT
CCN
WRITE
STATUS
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......