56
Table 20 — IGC Board LED Alarm Codes
NOTES:
1. There is a 3-second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will
be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is inter-
rupted.
LED FLASH
CODE
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET METHOD
PROBABLE CAUSE
On
Normal
Operation
— — —
Off
Hardware Failure
No gas heating.
—
Loss of power to the IGC. Check 5 amp fuse on
IGC, power to unit, 24V circuit breaker,
transformer, and wiring to the IGC.
1 Flash
Indoor Fan On/Off Delay
Modified
5 seconds subtracted from
On delay. 5 seconds
added to Off delay (3 min
max).
Power reset.
High temperature limit switch opens during heat
exchanger warm-up period before fan-on delay
expires. High temperature limit switch opens
within 10 minutes of heat call (W) Off. See Limit
Switch Fault.
2 Flashes
Limit Switch Fault
Gas valve and igniter Off.
Indoor fan and inducer On.
Limit switch closed, or heat
call (W) Off.
High temperature limit switch is open. Check the
operation of the indoor (evaporator) fan motor.
Ensure that the supply-air temperature rise is
within the range on the unit nameplate. Check
wiring and limit switch operation.
3 Flashes
Flame Sense Fault
Indoor fan and inducer On. Flame sense normal.
Power reset for LED reset.
The IGC sensed a flame when the gas valve
should be closed. Check wiring, flame sensor,
and gas valve operation.
4 Flashes
Four Consecutive Limit
Switch Fault
No gas heating.
Heat call (W) Off. Power
reset for LED reset.
4 consecutive limit switch faults within a single
call for heat. See Limit Switch Fault.
5 Flashes
Ignition Fault
No gas heating.
Heat call (W) Off. Power
reset for LED reset.
Unit unsuccessfully attempted ignition for 15
minutes. Check igniter and flame sensor
electrode spacing, gaps, etc. Check flame sense
and igniter wiring. Check gas valve operation and
gas supply.
6 Flashes
Induced Draft Motor Fault
If heat off: no gas heating.
If heat on: gas valve Off
and inducer On.
Inducer sense normal, or
heat call (W) Off.
Inducer sense On when heat call Off, or inducer
sense Off when heat call On. Check wiring,
voltage, and operation of IGC motor. Check
speed sensor wiring to IGC.
7 Flashes
Rollout Switch Lockout
Gas valve and igniter Off.
Indoor fan and inducer On. Power reset.
Rollout switch has opened. Check gas valve
operation. Check induced-draft blower wheel is
properly secured to motor shaft.
8 Flashes
Internal Control Lockout
No gas heating.
Power reset.
IGC has sensed internal hardware or software
error. If fault is not cleared by resetting 24 v
power, replace the IGC.
9 Flashes
Temporary Software
Lockout
No gas heating.
1 hour auto reset, or power
reset.
Electrical interference is disrupting the IGC
software.
LEGEND
IGC
— Integrated Gas Unit Control
LED
— Light-Emitting Diode
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......