112
O.20M
OAQ Sensor Value at 20mA
0 to 5000
2000
OAQ_20MA
25
H.4M
RH Sensor Value at 4mA
0 to 50
%
0
RH_4MA
26
H.20M
RH Sensor Value at 20mA
60 to 100
%
100
RH_20MA
26
OAU
OUTSIDE AIR UNIT CONFIG.
OAU_CFG
OA.TY
Outdoor Air Unit Type
0=No OAU
1=ERV Module
0: no FIOP
1: FIOP EnergyX
OAU_TYPE 36
OA.FC
Outside Air Fan Curve
0 to 999
1: 04
2: 05-06
3: 07
4: 08-12
5: 14
6: 17-20
7: 24-28
OAFANCRV
PE.FC
Exhaust Air Fan Curve
0 to 999
1: 04, 1ph, and
econ
2: 04, 3ph, and
econ
3: 04, 1ph, and
no econ
4: 04, 3ph, and
no econ
5: 05-06 1ph
6: 05-06 3ph
7: 07
8: 08-12
9: 14
10: 17-20 and
econ
11: 17-20 and no
econ
12: 24-28
PEFANCRV
U.RUN
OAU Unoccupied Operation
No/Yes
NO
UNOCCRUN
OAU.F
Shut Down on Fan Failure
No/Yes
Yes
FATALOAU
M.WHL
Modulating Wheel Install No/Yes
NO
MODWHEEL
OA.MN
Minimum Outside Air CFM
0 to 32000
CFM
375: 04
800: 05-06
1000: 07
2500: 08-12
3000: 14
4000: 17-20
5000: 24-28
MINOACFM
DCV.M
Min DCV Outside Air CFM
0 to 32000
CFM
100: 04
250: 05-06
600: 07
1000: 08-12
1500: 14-24
2000: 24-28
MINDCVSP
PEX.C
Power Exhaust Control
0=Offset CFM
1=BP
0 PEX_CTL
PE.OF
Power Exhaust CFM Offset
-17000 to 17000 CFM
- 200
EXOFFSET
BP.SP
Building Pressure Setpnt
- 0.25 to 0.25
in H2O 0.05
OAU_BPSP
OA.TM
Outside Air Tempering
Disable/Enable Disable
OATEMPER
TM.LO
OA Tempring Lockout Temp
0 to 80
°F
60
OATMPLOC
TM.SP
OA Tempring SAT Setpoint
35 to 80
°F
55
OATMPSPT
OAC.K
Outside Air CFM k Factor
0.8 to 1.2
1.0
OACFM_K
EXC.K
Exhaust Air CFM k Factor
0.8 to 1.2
1.0
EXCFM_K
OAFB
OAU Fan Boost Enable
No/Yes
No
EFB_ENBL
17
ALM.O
ALARM RELAY CONFIG.
ALM_CFG 33
A.SPC
SPT/SPRH Sensor Failure
No/Yes
Yes
SPACE_AL
A.SRT
SAT/RAT Sensor Failure
No/Yes
Yes
SATRATAL
A.OAT
OAT Thermistor Failure
No/Yes
Yes
OAT_AL
A.CS
Current Sensor Failure
No/Yes
No
CS_AL
A.CMP
Compressor Failure
No/Yes
Yes
COMP_AL
A.CKT
Refrig Circuit Failure
No/Yes
Yes
CKT_AL
A.SSP
SSP Transducer Failure
No/Yes
Yes
SSP_AL
A.SCT
SCT Thermistor Failure
No/Yes
Yes
SCT_AL
A.FAN
Indoor Fan Failure
No/Yes
Yes
FAN_AL
A.FIL
Dirty Filter
No/Yes
Yes
FILT_AL
A.TST
Thermostat Failure
No/Yes
Yes
TSTAT_AL
A.ECO
Economizer Failure
No/Yes
Yes
ECON_AL
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table H — Mode — Configuration (cont)
ITEM EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE
NO.
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......