APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
Table H — Mode — Configuration (cont)
ITEM EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE
NO.
FS.E1
Fan Speed - Free Cool Lo
0 to 100
%
67
FSPDECO1
FS.CL
Fan Speed - Mech Cooling
60 to 100
%
67
FSPDCOOL
FS.RH
Fan Speed - Reheat2
65 to 100
%
100
FSPDREHT
S.VFD
SUPPLY FAN VFD CONFIG
N.VLT
VFD1 Nominal Motor Volts
0 to 999
volts
230: 208/230v
1ph or 3ph
460: 460v
575: 575v
VFD1NVLT
N.AMP
VFD1 Nominal Motor Amps
0 to 999
amps
See VFD Motor
Parameters table
VFD1NAMP
N.FRQ
VFD1 Nominal Motor Freq
10 to 500
60
VFD1NFRQ
N.RPM
VFD1 Nominal Motor RPM
50 to 30000
See VFD Motor
Parameters table
VFD1NRPM
N.PWR
VFD1 Nominal Motor HPwr
0 to 500
See VFD Motor
Parameters table
VFD1NPWR
MAX.A
VFD1 Maximum Amps
0 to 999
amps
See VFD Motor
Parameters table
VFD1MAXA
M.DIR
VFD1 Motor Direction
0=FORWARD
1=REVERSE
0 VFD1MDIR
ACCL
VFD1 Acceleration Time
0 to 1800
secs
30
VFD1ACCL
DECL
VFD1 Deceleration Time
0 to 1800
secs
30
VFD1DECL
SW.FQ
VFD1 Switching Frequency
0 to 3
2
VFD1SWFQ
COOL
COOLING CONFIGURATION
COOL_CFG
N.CIR
Number of Circuits
1 or 2
1 (04- 07)
2 (08- 28)
MRT.C
CompressorMin On Time
120 to 999
sec
180
MIN_ON
MOT.C
Compressor Min Off Time
300 to 999
sec
300
MIN_OFF
RST.C
Runtime to Reset Strikes
120 to 999
sec
300
MIN_ON_S
C.DEC
Cool Stage Decrease Time
120 to 999
sec
300
STAGEDEC
C.INC
Cool Stage Increase Time
120 to 999
sec
450
STAGEINC
FOD.C
Fan-off Delay, Mech Cool
0 to 600
sec
30 (04- 05)
75 (06- 28)
ALM.N
Alert Each Strike
No/Yes
Yes
ALM_NOW
CA.LO
Circuit A Lockout Temp
0 to 100F
°F
40
0: Low ambient
or Humidimizer
FIOP
OATLCMPA 21
CB.LO
Circuit B Lockout Temp
0 to 100F
°F
40
0: Low ambient
or Humidimizer
FIOP
OATLCMPB 21
D.CMP
Diagnose Comp Safety
Disable/Enable Enable
DIAGCOMP
MX.SA
Max Suction Change CirA
0 to 100
PSIG
4 (04- 06, 17- 28)
6 (07- 12)
7 (14)
MX.SB
Max Suction Change CirB
0 to 100
PSIG
4 (04- 06, 17- 28)
6 (07- 12)
7 (14)
CS.A1
Current Sensing A1
Disable/Enable
Disable
A1_SENSE
CS.B1
Current Sensing B1
Disable/Enable
Disable
B1_SENSE
SAT
Supply Air Temperature
SA.PD
SAT Cool Demand (+) Level
0.5 to 10
^F
1
SAT_POS
SA.ND
SAT Cool Demand (-) Level
- 10 to - 0.5
^F
- 1
SAT_NEG
SAT.U
Minimum SAT Upper Level
35.0 to 65.0
°F
53 (04- 14)
56 (17- 28)
SAT.L
Minimum SAT Lower Level
35.0 to 65.0
°F
42 (04- 14)
46 (17- 28)
SATMIN_L 21
SPT
Space Temperature
CL.PD
SPT Cool Demand (+) Level
0.5 to 5
^F
1
DEM_POS
CL.ND
SPT Cool Demand (-) Level
- 5 to - 0.5
^F
- 1
DEM_NEG
C.LAG
Cool Thermal Lag Factor
0 to 5
1
COOL_LAG
SST
Low Suction Control
SST.O
Suction OK Temperature
10 to 50
°F
18
SSTOK
SST.1
Low Suction - Level 1
10 to 50
°F
20
SSTLEV1
SST.2
Low Suction - Level 2
5 to 50
°F
15
SSTLEV2
SST.3
Low Suction - Level 3
0 to 50
°F
10
SSTLEV3
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......