When free cooling is desired and allowed the wheel is not
needed to pre-condition the air therefore an economizer damp-
er (wheel bypass) is used to bring in the outside air directly to
the mixing box.
COMMUNICATION
The ERV relies on communication with the
Comfort
Link
controller to operate. The ERV monitors
Comfort
Link con-
troller points to determine operation. The ERV writes to
points in the
Comfort
Link controller to provide the user with
its running status. If communication is lost the ERV will shut
down and remain in the Off mode until communication is es-
tablished. Refer to the troubleshooting section for details on
communication failures. Table 11 shows the
Comfort
Link
points that the ERV monitors for operation and a brief de-
scription of their functions. Table 12 shows the
Comfort
Link
points that the ERV uses for its configurations and a brief de-
scription of each. Table 13 shows the
Comfort
Link points that
the ERV writes to based on its running status.
* These can be viewed under a variety of CCN tables with a CCN device.
† These can be viewed under a variety of menus on the scrolling marquee or Navigator™ display.
Table 11 — Inputs - Points the ERV Reads from
Comfort
Link Controller
CCN POINT*
SCROLLING
MARQUEE
POINT†
EXPANDED TEXT
RANGE
UNITS
DEFAULT
FUNCTION
NVO_MODE
nvoUnitStatus.mode
xxxx
Determine what mode RTU is in
OCCUPIED
OCC
Currently Occupied
No/Yes
Determine if RTU is occupied
IDFSTATE
Indoor Fan State
Off/On
Determine if the RTU indoor fan is running
FANSPEED
F.SPD
Commanded Fan Speed
xxx
%
Determine if the RTU indoor fan is running
ECONOCMD
EC.CP
Econo Commanded Position 0 to 100
%
Determine if the RTU commands free cooling
IAQ
IAQ
IAQ Level (sensor)
xxxx
Space CO
2
sensor level (PPM)
IAQIN
IAQ.S
IAQ Level (switch)
Low/High
Determine if CO
2
is high or low
SAT
SAT
Supply Air Temperature
xxx.x
°F
RTU supply air temp
OA_TEMP
OAT
Outdoor Air Temperature
xxx.x
°F
RTU Outdoor Temp
SPACE_T
SPT
Space Temperature
xxx.x
°F
Building Space Air Temp
RETURN_T
RAT
Return Air Temperature
xxx.x
°F
Building Return Air Temp
PE_1
PE.1
Power Exhaust 1 Relay
Off/On
N/A
PE_2
PE.2
Power Exhaust 2 Relay
Off/On
N/A
ECONO
EC.EN
Economizer Installed
No/Yes
No: no FIOP
Yes:
FIOP
Determine if there is a Economizer damper
(wheel Bypass)
IAQANCFG
IA.CF
IAQ Analog Input Config
0=No IAQ
1=DCV
2=Override IAQ
3=Ctrl Min Pos
0: no FIOP
1: FIOP
Tells if a sensor is installed for DCV or override
IAQANFAN
IA.FN
IAQ Analog Fan Config
0=Never
1=Occupied
2=Always
0
Tells if the ERV can run during unoccupied for
high CO
2
IAQINCFG
II.CF
IAQ Switch Input Config
0=No IAQ
1=DCV N/O
2=DCV N/C
3=Override N/O
4=Override N/C
0
Tells if a switch is installed for DCV or override
IAQINFAN
II.FN
IAQ Switch Fan Config
0=Never
1=Occupied
2=Always
0
Tells if the ERV can run during unoccupied for
high CO
2
DAQ_LOW
AQD.L
AQ Differential Low
0 to 5000
100
Sets indoor/outdoor PPM difference to start
ventilating more
DAQ_HIGH
AQD.H
AQ Differential High
0 to 5000
700
Sets indoor/outdoor PPM at which max vent
occurs
IAQOVPOS
OVR.P
IAQ Override Position
0 to 100
%
100
Sets OA fan speed during override
S_OADMPR
OA.DM
OAU 2 - position Damper
Close/Open
Close
Test damper while in test mode
S_WHEEL
WHL
OAU Wheel Test
0 to100
%
0
Test wheel while in test mode
S_OAFAN
OA.OF
OAU OA Fan Speed Test
0 to100
%
0
Test intake fan(s) while in test mode
S_EXFAN
OA.XF
OAU PE Fan Speed Test
0 to100
%
0
Test exhaust fan(s) while in test mode
S_OAHEAT
OA.HT
OAU Tempring Heater Test 0 to 100
%
0
Test tempering heater while in test mode
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......