
128
APPENDIX C — VARIABLE FREQUENCY DRIVE (VFD) (cont)
* This alarm is not indicated by a relay output, even when the relay out-
put is configured to indicate alarm conditions, parameter 1401 RELAY
OUTPUT = 5 (ALARM) or 16 (FLT/ALARM).
Table W — Alarm Codes
ALARM CODE ALARM NAME IN PANEL
DESCRIPTION AND RECOMMENDED CORRECTIVE ACTION
2001
—
Reserved
2002
—
Reserved
2003
—
Reserved
2004
DIR LOCK
The change in direction being attempted is not allowed. Do not attempt to change the direction of motor
rotation, or Change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe).
2005
I/O COMM
Field bus communication has timed out. Check fault setup (3018 COMM FAULT FUNC and 3019 COMM
FAULT TIME). Check communication settings (Group 51 or 53 as appropriate). Check for poor
connections and/or noise on line.
2006
Al1 LOSS
Analog input 1 is lost, or value is less than the minimum setting. Check input source and connections.
Check the parameter that sets the minimum (3021) and the parameter that sets the Alarm/Fault
operation (3001).
2007
Al2 LOSS
Analog input 2 is lost, or value is less than the minimum setting. Check input source and connections.
Check parameter that sets the minimum (3022) and the parameter that sets the Alarm/Fault operation
(3001).
2008
PANEL LOSS
Panel communication is lost and either the VFD is in local control mode (the control panel displays
HAND), or the VFD is in remote control mode (AUTO) and is parameterized to accept start/stop,
direction or reference from the control panel. To correct, check the communication lines and
connections, Parameter 3002 PANEL LOSS, and parameters in groups 10 COMMAND INPUTS and 11
REFERENCE SELECT (if drive operation is REM).
2009
—
Reserved
2010
MOT OVERTEMP
Motor is hot, based on either the VFD estimate or on temperature feedback. This alarm warns that a
Motor Overload fault trip may be near. Check for overloaded motor. Adjust the parameters used for the
estimate (3005 through 3009). Check the temperature sensors and Group 35 parameters.
2011
UNDERLOAD
Motor load is lower than expected. This alarm warns that a Motor Underload fault trip may be near.
Check that the motor and drive ratings match (motor is NOT undersized for the drive). Check the settings
on parameters 3013 to 3015.
2012
MOTOR STALL
Motor is operating in the stall region. This alarm warns that a Motor Stall fault trip may be near.
2013*
AUTORESET
This alarm warns that the drive is about to perform an automatic fault reset, which may start the motor.
To control automatic reset, use parameter group 31 (AUTOMATIC RESET).
2014
AUTOCHANGE
This alarm warns that the PFA autochange function is active. To control PFA, use parameter group 81
(PFA) and the Pump Alternation macro.
2015
PFA INTERLOCK
This alarm warns that the PFA interlocks are active, which means that the drive cannot start any motor
(when Autochange is used), or a speed regulated motor (when Autochange is not used).
2016
—
Reserved
2017*
OFF BUTTON
This alarm indicates that the OFF button has been pressed.
2018
PID SLEEP
This alarm warns that the PID sleep function is active, which means that the motor could accelerate
when the PID sleep function ends. To control PID sleep, use parameters 4022 through 4026 or 4122
through 4126.
2019
ID RUN
The VFD is performing an ID run.
2020
OVERRIDE
Override mode is activated.
2021
START ENABLE 1
MISSING
This alarm warns that the Start Enable 1 signal is missing. To control Start Enable 1 function, use
parameter 1608. To correct, check the digital input configuration and the communication settings.
2022
START ENABLE 2
MISSING
This alarm warns that the Start Enable 2 signal is missing. To control Start Enable 2 function, use
parameter1609. To correct, check the digital input configuration and the communication settings.
2023
EMERGENCY STOP
Emergency stop is activated.
Содержание /50HC 04-28
Страница 61: ...61 Fig 21 Saturated Condensing Temperature Thermistor Location 48 50HC 14 SCT B SCT A CIRCUIT B CIRCUIT A ...
Страница 69: ...69 Fig 24 Typical Control Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 70: ...70 Fig 25 Typical Power Diagram for 48HC 04 14 Units 48HC 08 09 shown ...
Страница 71: ...71 Fig 26 Typical Control Diagram for 50HC 04 14 Units 50HC 14 shown ...
Страница 72: ...72 Fig 27 Typical Power Diagram for 50HC 04 14 Units 50HC 14 Non Humidi MiZer shown ...
Страница 73: ...73 Fig 28 Typical Control Diagram 48HC 17 28 Units ...
Страница 74: ...74 Fig 29 Typical Control Diagram 50HC 17 28 Units ...
Страница 75: ...75 Fig 30 Typical Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 76: ...76 Fig 31 Typical Non Humid MiZer Power Diagram and Component Arrangement 48 50HC 17 28 Units ...
Страница 89: ...89 Fig 42 Modulating ERV Wiring Schematic ...
Страница 90: ...90 Fig 43 EnergyX ERV Control Box Component Layouts ...
Страница 101: ...101 Fig 59 Exhaust Fan Assembly Removal Exhaust Fan Assembly ...
Страница 141: ......