12.2.12.2 - Installation, operation, adjustments
The instructions given for standard units (BPHE) are also
valid for units with option 280 (STHE), including those relating
to the operating range (Application data section), to frost
protection (Water connection section), and to the installation
settings (Adjusting the nominal flow rate of the installation).
However, it should be noted that the data in the sub-sections
must be replaced by the table and graph below:
-
Water type heat exchanger water flow rate - Units without
hydraulic module
-
Pressure drop curve for the water type heat exchanger
and standard water inlet/outlet piping
30RBM/30RBP
Minimum flow rate
(1)
(l/s)
Maximum flow rate
(2)
(l/s)
160
2,9
18,3
180
3,2
18,3
200
3,6
18,3
220
3,8
18,3
260
4,6
18,3
(1) Minimum flow rate for maximum allowable water temperature difference conditions (10K) under
Eurovent conditions
(2) Maximum flow rate for a pressure drop of 100 kPa in the shell and tube exchanger
10
100
1,0
10,0
100,0
Pe
rt
es
d
e
ch
ar
ge
, k
Pa
Débit, l/s
1
1 30RBM/30RBP 160 to 260
12.2.12.3 - Combination with the Brine Option (Options 5B or 6B)
The instructions given for standard units (BPHE) are also
valid for units with option 280 (STHE), with the exception of:
-
the minimum exchanger water outlet temperature which
is limited to -12°C when used with the low-temperature
brine solution (Option 6B). It remains unchanged and
limited to 0°C when using the medium-temperature brine
solution (Option 5B).
-
the refrigerant charge with Option 6B - the adjusted
values are given in the following table:
30RBM/P + option 280 + option 6B
160
180
200
220
260
Refrigerant
(1)
R410A
Circuit A
kg
9,80 12,10 12,10 13,10 13,10
tCO
2
e
20,5 25,3 25,3 27,4 27,4
Circuit B
kg
13,30 13,30 13,30 13,30 13,30
tCO
2
e
27,8 27,8 27,8 27,8 27,8
(1) Values are guidelines only. Refer to the unit name plate.
Pr
essur
e dr
ops (kP
a)
Flow rate, l/s