62
12.2.10 - DX Free Cooling option (Options 118A and 118B)
The DX Free Cooling option is used to produce chilled water when the ambient air temperature is lower than the temperature
of the water to be cooled, without activating the compressors [the compressors can be used for a few seconds during a Free
Cooling cycle to transfer the refrigerant charge to the Free Cooling circuit – see Operation].
Only the unit fans and a low power pump that circulates the refrigerant in the Free Cooling circuit operate to generate cooling power.
This ensures particularly high efficiency during operation in Free Cooling mode.
Option 118A (Free Cooling on both circuits) is available for units from size 220.
Option 118B (Free Cooling on one circuit) is available across the entire range.
12.2.10.1 - Physical properties of units with the Free Cooling option
30RBM/30RBP option 118A (Free Cooling on 2 circuits)
160
180
200
220
260
300
330
360
400
430
470
520
30RBM - Operating weight
(1)
Standard unit + option 118A
kg
-
-
-
1447
1468
1939 1975 2147
2203
2619 2637
2833
Unit with option 15 + option 118A
kg
-
-
-
1555
1576
2065 2101
2290 2347 2781
2800 3013
Unit with option 15 + option 116S + 118A
kg
-
-
-
1694 1730
2225 2305
2494
2550 3024 3041
3293
30RBP - Operating weight
(1)
Standard unit + option 118A
kg
-
-
-
1483 1505
1975
2011 2183 2240
2677 2695 2899
Unit with option 15 + option 118A
kg
-
-
-
1591
1613 2101
2137 2327
2384
2839 2857 3079
Unit with option 15 + option 116S + 118A
kg
-
-
-
1730 1767
2261 2341 2530
2587
3081
3098 3359
30RBM/30RBP - Refrigerant
R410A
Circuit A
(1)
kg
-
-
-
13,9
14,6
16,7
17,6
24,8
24,3
27,5
25,5
31,6
tCO
2
e
-
-
-
29,0
30,5
34,9
36,7
51,8
50,7
57,4
53,2
65,9
Circuit B
(1)
kg
-
-
-
14,0
14,6
25,0
24,7
25,4
25,4
29,5
30,3
31,8
tCO
2
e
-
-
-
29,2
30,5
52,2
51,6
53,0
53,0
61,6
63,3
66,3
30RBM/30RBP option 118B (Free Cooling on 1 circuit)
30RBM - Operating weight
(1)
Standard unit + option 118B
kg
1248 1286 1286 1416
1457 1910 1946
2110 2166 2581
2599 2793
Unit with option 15 + 118B
kg
1331 1368
1369
1524 1565 2036
2072
2253 2310
2743 2762 2973
Unit with option 15 + option 116S + 118B
kg
1470
1508 1508 1663
1719 2196 2276 2457
2513
2986
3003 3253
30RBP - Operating weight
(1)
Standard unit + option 118B
kg
1284 1322 1322 1452
1474 1946 1982
2146 2203
2639 2657 2859
Unit with option 15 + 118B
kg
1366 1405 1405 1560 1582
2072
2108
2290 2347
2801
2819 3039
Unit with option 15 + option 116S + 118B
kg
1505 1544 1545
1699 1736
2232 2312
2493
2550 3043 3060
3319
30RBM/30RBP - Refrigerant
R410A
Circuit A
(1)
kg
8,4
10,9
10,9
12,6
13,1
14,7
15,4
20,3
21,1
23,5
23,5
26,8
tCO
2
e
17,5
22,8
22,8
26,3
27,4
30,7
32,2
42,4
44,1
49,1
49,1
55,9
Circuit B
(1)
kg
14,0
14,1
13,7
14,0
14,6
25,0
24,7
25,4
25,4
29,5
30,3
31,8
tCO
2
e
29,1
29,4
28,6
29,2
30,5
52,2
51,6
53,0
53,0
61,6
63,3
66,3
(1) Weights are guidelines only. Refer to the unit name plate.