19
5.2 - Physical data 30RBP 160-520
30RBP
160
180
200
220
260
300
330
360
400
430
470
520
Sound levels
Standard unit
Sound power
(3)
dB(A)
91
92
92
92
92
93
93
93
93
94
94
94
Sound pressure at 10 m
(4)
dB(A)
59
60
60
60
60
60
60
61
61
62
62
62
Standard unit + option 15
(1)
Sound power
(3)
dB(A)
89
90
90
90
90
91
91
92
92
93
93
93
Sound pressure at 10 m
(4)
dB(A)
57
58
58
58
58
59
59
60
60
61
61
61
Standard unit + option 15LS
(1)
Sound power
(3)
dB(A)
85
85
85
86
86
86
86
87
87
88
88
88
Sound pressure at 10 m
(4)
dB(A)
53
53
53
54
54
54
54
55
55
55
55
56
Dimensions - Standard unit
Length
mm
2410
3604
4797
Width
mm
2253
2253
2253
Height
mm
2322
2322
2322
Unit length with water buffer tank module opt
mm
3604
4798
5991
Operating weight
(2)
Standard unit
kg
1240
1278
1278
1407
1429
1882
1918
2082
2139
2576
2594
2796
Standard unit + option 15
(1)
kg
1323
1361
1361
1515
1537
2008
2044
2226
2283
2738
2756
2976
Standard unit + option 15 + option 116W
(1)
kg
1462
1500
1500
1655
1692
2168
2248
2429
2486
2980
2997
3257
Standard unit + option 15 + option 116W +
water buffer tank module
kg
2409
2444
2444
2599
2635
3108
3188
3365
3422
3912
3929
4185
Compressors
Hermetic Scroll 48,3 rps
Circuit A
1
1
1
2
2
2
2
3
3
3
3
4
Circuit B
2
2
2
2
2
3
3
3
3
4
4
4
No. of control stages
3
3
3
4
4
5
5
6
6
7
7
8
Refrigerant
(2)
R410A
Circuit A
kg
8,40
10,90
10,90
12,60
13,10
14,70
15,40
20,30
21,10
23,50
23,50
26,75
tCO
2
e
17,5
22,8
22,8
26,3
27,4
30,7
32,2
42,4
44,1
49,1
49,1
55,9
Circuit B
kg
12,25
12,60
12,60
12,70
13,10
20,20
20,20
20,40
22,20
26,70
26,80
26,95
tCO
2
e
25,6
26,3
26,3
26,5
27,4
42,2
42,2
42,6
46,4
55,7
56,0
56,3
Control
Smart View Control
Minimum capacity
%
33%
33%
33%
25%
25%
20%
20%
17%
17%
14%
14%
13%
Condensers
Aluminium micro-channel coils (MCHE)
Fans - Standard unit
FLYING BIRD 4 axial fans with rotating impeller
Quantity
3
4
4
4
4
5
5
6
6
7
7
8
Maximum total air flow
l/s
13542 18056 18056 18056 18056
22569 22569 27083 27083 31597 31597
36111
Maximum rotation speed
rps
16
16
16
16
16
16
16
16
16
16
16
16
Evaporator
Dual-circuit plate heat exchanger
Water volume
l
15
15
15
15
19
27
35
33
42
44
47
53
Max. water-side operating pressure without
hydraulic module
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Hydraulic module (option)
Pump, victaulic screen filter, relief valve, water and air drain valve, pressure sensors, expansion vessel
(option)
Pump
Centrifugal pump, monocell, 48,3 r/s, low- or high-pressure (as required), single or dual (as required)
Expansion vessel volume
l
50
50
50
50
50
80
80
80
80
80
80
80
Max. water-side operating pressure with
hydraulic module
kPa
400
400
400
400
400
400
400
400
400
400
400
400
Water connections with or without
hydraulic module
Victaulic
®
type
Connections
in
3
3
3
3
3
4
4
4
4
4
4
4
Outside diameter
mm
88,9
88,9
88,9
88,9
88,9
114,3
114,3
114,3
114,3
114,3
114,3
114,3
Casing paint
Colour code RAL 7035
(1) Options: 15 = low noise level, 15LS = very low noise level, 116W = variable speed high-pressure dual-pump hydraulic module.
(2) Values are guidelines only. Refer to the unit name plate.
(3) in dB ref=10
-12
W, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). Measured in accordance with ISO 9614-1 and certified
by Eurovent.
(4) In dB ref 20µPa, 'A' weighted. Declared dual-number noise emission values in accordance with ISO 4871 with an associated uncertainty of +/-3dB(A). For information, calculated from the sound power