5.6 - Electrical data notes for the hydraulic module
The pumps fitted to these units have motors which meet efficiency class IE2 for motors < 7.5kW and IE3 for motors > 7.5kW.
The additional electrical data required
(1)
is as follows:
For the low-pressure single pump motors of 30RBM/RBP 160-520 units (option 116T)
No.
(2)
Description
(3)
Units
30RBM/30RBP
160
180 200 220
260
300 330
360
400 430 470 520
1
Nominal efficiency at full load and nominal voltage
%
85,7 85,7 85,7 85,7 85,7 87,5 87,5 87,5 89,9 89,9 89,9
89
1
Nominal efficiency at 75% of full load and nominal voltage
%
86,9 86,9 86,9 86,9 86,9 88,2 88,2 88,2 90,4 90,4 90,4
90
1
Nominal efficiency at 50% of full load and nominal voltage
%
86,4 86,4 86,4 86,4 86,4 87,5 87,5 87,5 89,6 89,6 89,6 89,7
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4
Manufacturer's name and trademark, commercial registration
number and manufacturer's head office
-
Same as above
5
Product's model number
-
Same as above
6
Number of motor poles
-
2
2
2
2
2
2
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
kW
2,2
2,2
2,2
2,2
2,2
3
3
3
4
4
4
5,5
7-2
Maximum input power (400 V)
(4)
kW
2,80 2,80 2,80 2,80 2,80 3,81 3,81 3,81 4,96 4,96 4,96 6,80
8
Rated input frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
9-1
Nominal voltage
V
3 X 400
9-2
Maximum current drawn (400 V)
(5)
A
4,92 4,92 4,92 4,92 4,92 6,81 6,81 6,81 8,27 8,27 8,27 11,30
10
Nominal speed
rps - rpm
48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12
Operating conditions for which the motor is specifically designed
I- Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
IV - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or
in the specific conditions given in the Carrier selection programs.
V - Potentially explosive atmospheres
-
Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum operating current draw for a unit with hydraulic module, add the maximum unit current draw from the electrical data table to the pump current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
For the low-pressure dual pump motors of 30RBM/RBP 160-520 units (option 116U)
No.
(2)
Description
(3)
Units
30RBM/30RBP
160
180 200 220
260
300 330
360
400 430 470 520
1
Nominal efficiency at full load and nominal voltage
%
84,9 84,9 85,7 85,7 87,5 87,5 87,5 87,5 89,9 89,9 89,9
89
1
Nominal efficiency at 75% of full load and nominal voltage
%
86,4 86,4 86,9 86,9 88,2 88,2 88,2 88,2 90,4 90,4 90,4
90
1
Nominal efficiency at 50% of full load and nominal voltage
%
85,9 85,9 86,4 86,4 87,5 87,5 87,5 87,5 89,6 89,6 89,6 89,7
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4
Manufacturer's name and trademark, commercial registration
number and manufacturer's head office
-
Same as above
5
Product's model number
-
Same as above
6
Number of motor poles
-
2
2
2
2
2
2
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
kW
1,5
1,5
2,2
2,2
3
3
3
3
4
4
4
5,5
7-2
Maximum input power (400 V)
(4)
kW
1,94 1,94 2,80 2,80 3,81 3,81 3,81 3,81 4,96 4,96 4,96 6,80
8
Rated input frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
9-1
Nominal voltage
V
3 X 400
9-2
Maximum current drawn (400 V)
(5)
A
3,41 3,41 4,92 4,92 6,81 6,81 6,81 6,81 8,27 8,27 8,27 11,30
10
Nominal speed
rps - rpm
48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12
Operating conditions for which the motor is specifically designed
I- Altitudes above sea level
m
< 1000(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or
in the specific conditions given in the Carrier selection programs.
V - Potentially explosive atmospheres
-
Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum operating current draw for a unit with hydraulic module, add the maximum unit current draw from the electrical data table to the pump current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.