background image

23

5.9 - Electrical data notes

  

Electrical data for 30RBM/30RBP units:

• 

30RBM/30RBP units have a single power connection point located immediately 

upstream of the main switch.

• 

Control box includes:

 

-

 Main disconnect switch,

 

-

Start-up and motor protection devices for each compressor, fans and pumps,

 

-

Control devices.

• 

Field connections:

 

All connections to the system and the electrical installations must be in accordance 

with all applicable codes.

• 

30RBM/30RBP units are designed and built to ensure conformance with these 

codes. The recommendations of European standard EN 60204-1 (corresponds 

to  IEC  60204-1)  (machine  safety  -  electrical  machine  components  -  part  1: 

general regulations) are specifically taken into account, when designing the 

electrical equipment.

Notes

• 

Generally the recommendations of IEC 60364 are accepted as compliance with 

the requirements of the installation regulation.

• 

Conformance with EN 60204-1 is the best means of ensuring compliance (§1.5.1) 

with the Machinery Directive. 

Annex B of standard EN 60204-1 specifies the electrical features used for the 

operation of the units.

• 

Operating conditions of 30RBM/30RBP units are described below:

1.  Physical environment*

The classification of environment is specified in standard EN 60364:

 

-

Outdoor installation*,

 

-

Ambient temperature range: minimum temperature -20°C to +48°C**,

 

-

Altitude: AC1 of 2000 m or less (for the hydraulic module, see the paragraph 

"Electrical data for the hydraulic module"),

 

-

Presence of hard solid: Class AE3 (no significant dust present)*,

 

-

Presence of corrosive and polluting substances, class AF1 (negligible),

 

-

Competence of persons: BA4 (Persons wise).

2.  Compatibility for low-frequency conducted disturbances according to class 2 

levels as per the IEC61000-2-4 standard:

 

-

Power supply frequency variation: +- 2Hz

 

-

Phase imbalance : 2%

 

-

Total Voltage Harmonic Distortion (THDV): 8%

3.  The neutral wire (N) must not be connected directly to the unit (if necessary use 

a transformer).

4.  Overcurrent protection of the power supply conductors is not provided with the 

unit.

5.  The factory-fitted disconnect switch(es)/circuit breaker(s) are of a type suitable 

for  power  interruption  in  accordance  with  EN  60947-3  (corresponds  to  IEC 

60947-3).

6.  The units are designed for connection to TN networks (IEC 60364). In IT networks, 

if noise filters are integrated into the variable frequency drive(s), this will render 

the  units  unsuitable  for  their  intended  purpose.  In  addition,  the  equipment 

characteristics in case of insulation failure are modified. Provide a local earth; 

consult competent local organisations to complete the electrical installation.

 

30RBM/30RBP  machines  are  designed  for  use  in  domestic/residential  and 

industrial environments:

 

Machines that are not equipped with variable speed drives comply with the 

standard regulations.

 

- 61000-6-3: General standards - Standard emission for residential, commercial 

and light industry,

 

- 61000-6-2: General standards - Immunity for industrial environments

 

Units equipped with variable frequency drive(s) (RBP, options: 28, 116V, 116W) 

are in accordance with standard EN61800 - 3 electric power variable speed drives 

-  part  3:  EMC  requirements  and  specific  test  methods  for  the  following 

classifications:-:

  

Use in the first and second environments***.

 

- Category C2 applicable in the first environment, to stationary devices designed 

to be installed and commissioned by a professional.

 

Warning: In a residential environment, this product may cause radio 

interference in which case additional mitigation measures could be 

required.

• 

Leakage currents: If protection by monitoring the leakage currents is necessary 

to ensure the safety of the installation, the presence of additional leakage currents 

introduced by the use of variable frequency drive(s) in the unit must be considered.

 

In particular, the reinforced immunity protection types and/or a control value not 

lower than 150 mA are recommended when selecting differential protective 

devices.

•  Capacitors integrated as part of option 231 can generate electrical 

disturbances in the installation the unit is connected to. The presence of these 

capacitors must be considered during the electrical study prior to the start-up.

 

Note: If particular aspects of an actual installation do not conform to the 

conditions described above, or if there are other conditions which should 

be considered, always contact your local Carrier representative.

*  The required protection level for this class is IP43BW (according to reference 

document  IEC  60529).  All  30RQM/30RQP  units  are  IP44CW  and  fulfil  this 

protection condition.

**  The maximum allowable ambient temperature for units equipped with the Power 

factor correction option is +40°C 

***  - Example of installations of the first environment: Commercial and residential 

buildings.

 

- Example of installations of the second environment: industrial zones, technical 

rooms powered from a dedicated transformer.

Содержание 30RBM 160

Страница 1: ...ION OPERATION AND MAINTENANCE INSTRUCTIONS Air Cooled Liquid Chillers 30RBM 160 520 30RBP 160 520 Translation of the original document Unit with low noise level option Nominal cooling capacity 164 528...

Страница 2: ...connection disconnect switch 25 7 APPLICATION DATA 26 7 1 Operating range 26 7 2 Minimum heat transfer fluid flow rate units without factory fitted hydraulic module 27 7 3 Maximum heat transfer fluid...

Страница 3: ...ANCE 67 13 1 Level 1 maintenance 67 13 2 Level 2 maintenance 67 13 3 Level 3 maintenance 68 13 4 Tightening of the electrical connections 68 13 5 Tightening torques for the main fastenings 68 13 6 Air...

Страница 4: ...itch x External relief valve 3 x Rupture disk x Fusible plug x Heat transfer fluid side External relief valve 4 4 1 Classified for protection in normal service situations 2 Classified for protection i...

Страница 5: ...rations Use safety goggles and safety gloves All precautions concerning handling of refrigerant must be observed in accordance with local regulations If a leak occurs or if the refrigerant becomes con...

Страница 6: ...the European Union this legislation notably includes regulation No 517 2014 known as F Gas Ensure that refrigerant is never released to the atmosphere when the equipment is installed maintained or sen...

Страница 7: ...ports of the periodical checks by the user or the operator must be included in the monitoring and maintenance log Repair Any repair or modification including replacement of removable parts Must comply...

Страница 8: ...ase Only use dry nitrogen for leak tests possibly with an appropriate tracer gas A failure to observe the above recommendations can have serious or even fatal consequences and damage the installations...

Страница 9: ...NG AND POSITIONING 3 1 Handling It is strongly recommended that a specialised lifting company is employed to unload the machine Do not remove the subbase or the packaging until the unit is in its fina...

Страница 10: ...teristics and the comfort level required and should be made by technical specialists There is adequate space above and around the unit for air to circulate and for access to the components see dimensi...

Страница 11: ...maintenance and air flow 2 Clearance recommended for coil removal Water inlet Water outlet Air outlet do not obstruct Control box NOTE Non contractual drawings When designing a system refer to the ce...

Страница 12: ...recommended for coil removal Water inlet Water outlet Air outlet do not obstruct Control box NOTE Non contractual drawings When designing a system refer to the certified dimensional drawings provided...

Страница 13: ...e and air flow 2 Clearance recommended for coil removal Water inlet Water outlet Air outlet do not obstruct Control box NOTE Non contractual drawings When designing a system refer to the certified dim...

Страница 14: ...ct Control box NOTE Non contractual drawings When designing a system refer to the certified dimensional drawings provided with the unit or available on request For the location of fixing points weight...

Страница 15: ...and air flow 2 Clearance recommended for coil removal Water inlet Water outlet Air outlet do not obstruct Control box NOTE Non contractual drawings When designing a system refer to the certified dimen...

Страница 16: ...ct Control box NOTE Non contractual drawings When designing a system refer to the certified dimensional drawings provided with the unit or available on request For the location of fixing points weight...

Страница 17: ...e example below to avoid recycling hot air between the units 1500mm min 1500mm min 4 5 Distance to the wall Plots Antivibratiles S H h To guarantee correct operation in most cases If h H S minimum 3 m...

Страница 18: ...0 56 3 Control Smart View Control Minimum capacity 33 33 33 25 25 20 20 17 17 14 14 13 Condensers Aluminium micro channel coils MCHE Fans Standard unit FLYING BIRD 4 axial fans with rotating impeller...

Страница 19: ...iew Control Minimum capacity 33 33 33 25 25 20 20 17 17 14 14 13 Condensers Aluminium micro channel coils MCHE Fans Standard unit FLYING BIRD 4 axial fans with rotating impeller Quantity 3 4 4 4 4 5 5...

Страница 20: ...158 176 197 216 237 255 276 316 Max operating input power 2 Circuit A B kW 81 88 99 108 129 145 162 178 194 210 226 259 Cosine Phi unit at maximum power 2 0 88 0 88 0 88 0 88 0 88 0 88 0 88 0 88 0 88...

Страница 21: ...ent draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current draw 6 Above 1000 m a degradation of 3 for each 500 m should be taken int...

Страница 22: ...above sea level m 1000 6 II Ambient air temperature C 40 III Maximum operating temperature C Please refer to the operating conditions given in this manual or in the specific conditions given in the C...

Страница 23: ...ve s this will render the units unsuitable for their intended purpose In addition the equipment characteristics in case of insulation failure are modified Provide a local earth consult competent local...

Страница 24: ...he hydraulic module The study includes the standardised installation cases according to IEC 60364 cables with PVC 70 C or XLPE 90 C insulation with copper core routing in accordance with table 52C of...

Страница 25: ...ing and or insulation characteristics of the conductors ensures double electrical insulation The conductors should be fixed together inside the electrical box to prevent contact between the end of the...

Страница 26: ...nsidered in case of container shipment and temperatures over 52 C Operating range 30RBM 160 520 units 30 20 10 0 10 20 30 40 50 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 48 52 Charge partielle C...

Страница 27: ...hydraulic module A variable water heat exchanger flow can be used in standard units The flow rate must be higher than the minimum flow given in the table of permissible flow rates and must not vary b...

Страница 28: ...1 Maximum flow rate l s Single Dual Single Dual 160 2 8 3 2 12 2 10 3 180 2 8 3 2 12 2 10 3 200 2 8 2 5 12 2 12 2 220 2 8 2 5 12 2 12 2 260 4 2 7 14 3 15 300 3 1 3 7 20 2 20 2 330 3 4 3 7 20 2 20 2 3...

Страница 29: ...360 units Pressure drop kPa Water flow rate l s 1 2 3 4 5 100 10 1 0 10 0 100 0 1 2 3 5 4 1 30RBM 30RBP 160 200 2 30RBM 30RBP 260 3 30RBM 30RBP 300 4 30RBM 30RBP 330 5 30RBM 30RBP 360 30RBM 30RBP 400...

Страница 30: ...air bleed devices and tools and equipment suitable for the products The heat transfer fluid should be filled and drained using devices fitted to the water circuit by the installer Never use the unit h...

Страница 31: ...ure information for the water exchanger inlet see Control manual 10 Pressure sensor Note Provides pressure information for the water exchanger outlet see Control manual 11 Check valve if dual pump 12...

Страница 32: ...on previous page Example Single pump Example Dual pump Figure 3 Water connections with hydraulic module and with buffer tank module option A 15 5 23 6 Coupling for expansion vessel option 293 Presenc...

Страница 33: ...remainder of the system is the responsibility of the installer The plate heat exchanger and all the components of the water circuit can be protected against freezing by draining the entire machine co...

Страница 34: ...which must be between the values shown in the operating limits table application data If frost protection is dependent on electric heaters never de energize the unit when frost protection is required...

Страница 35: ...the pump pressure flow rate curve to obtain the nominal flow rate at the desired operation point This is checked by reading the pressure drop on the unit plate heat exchanger internal piping As the ex...

Страница 36: ...the overall pressure drop in the system is too low compared to the available static pressure generated by the pump In this case close the control valve item 22 and read the new flow rate value Repeat...

Страница 37: ...eached Read the value of the flow on the user interface Let the pump run for 2 hours continuously to clean up the system s hydraulic circuit presence of contaminating solids Perform another reading of...

Страница 38: ...ue the system will stop once it reaches the maximum flow rate or maximum frequency which will result in a Delta T above the setpoint Contact the manufacturer s service department to implement the proc...

Страница 39: ...reduced High pressure pumps Single pumps Sizes 160 400 Available static pressure kPa Water flow rate l s 50 70 90 110 130 150 170 190 210 230 250 270 290 0 5 10 15 20 25 1 2 3 5 4 6 1 30RBM 30RBP 160...

Страница 40: ...er flow rate l s 1 30RBM 30RBP 160 to 220 2 30RBM 30RBP 260 3 30RBM 30RBP 300 4 30RBM 30RBP 360 5 30RBM 30RBP 330 6 30RBM 30RBP 400 Sizes 430 520 50 70 90 110 130 150 170 190 210 230 250 270 290 310 0...

Страница 41: ...5 10 15 20 1 2 3 4 5 1 30RBM 30RBP 160 to 220 2 30RBM 30RBP 260 3 30RBM 30RBP 300 4 30RBM 30RBP 360 5 30RBM 30RBP 330 Sizes 400 520 Available static pressure kPa Water flow rate l s 20 40 60 80 100 12...

Страница 42: ...4 6 7 1 30RBM 30RBP 160 to 180 2 30RBM 30RBP 200 to 220 3 30RBM 30RBP 260 4 30RBM 30RBP 300 5 30RBM 30RBP 330 6 30RBM 30RBP 360 7 30RBM 30RBP 400 Sizes 430 520 Available static pressure kPa Water flow...

Страница 43: ...Check the protection against mechanical damage Check the protection against heat Check the protection of moving parts Check accessibility for maintenance or repair and to check the piping Verify the...

Страница 44: ...in temperature between the exchanger inlet and outlet will be too high This is why pressure drops must be minimised Make sure this difference is within the values on the curve refer to the chapter Wat...

Страница 45: ...3 59 4 15 Pressure at optimum energy efficiency Pa 170 216 95 195 90 170 Nominal Speed rpm 954 1127 712 966 710 950 Specific ratio 1 002 1 002 1 002 1 002 1 002 1 002 Relevant information to facilita...

Страница 46: ...terials supplied by the manufacturer comply with this requirement NOTE Monitoring in operation Follow local regulations on the monitoring of pressure equipment The user or operator is usually requeste...

Страница 47: ...EV41 EV32 EV42 EV31 EV31 11 14 Variable speed ventilation The variable speed drives on the fans are used to optimise the efficiency of the unit depending on the conditions of use air temperature circ...

Страница 48: ...of free high temperature hot water simultaneously with chilled water production or hot water for Heat pump 30RBM 30RBP 160 520 Master slave operation 58 Unit equipped with supplementary water outlet...

Страница 49: ...nt electrical power input compliance with minimum power factor limit set by electricity providers 30RBM 30RBP 160 520 Enviro Shield anti corrosion protection 262 Coating by conversion process which mo...

Страница 50: ...exchanger is installed as standard with air cooled exchangers on the compressor discharge line on each circuit The control is configured for the partial heat recovery option in the factory see the sec...

Страница 51: ...dimensions are in mm 1 Clearances required for maintenance and air flow 2 Clearance recommended for coil removal Water inlet Water outlet Air outlet do not obstruct Control box NOTE Non contractual dr...

Страница 52: ...1 Clearances required for maintenance and air flow 2 Clearance recommended for coil removal Water inlet Water outlet Air outlet do not obstruct Control box NOTE Non contractual drawings When designing...

Страница 53: ...ed dimensional drawings Key All dimensions are in mm 1 Clearances required for maintenance and air flow 2 Clearance recommended for coil removal Water inlet Water outlet Control box NOTE Non contractu...

Страница 54: ...ondenser coils 5 Expansion valve EXV 6 Damage limitation accessory in case of a fire relief valve 7 Electric heater to protect the desuperheater against frost not supplied 8 Desuperheater insulation n...

Страница 55: ...prise a valve and an expansion vessel which must be selected to take the volume of the water loop and the maximum possible temperature into account 120 C in the event that pump item 20 stops running 1...

Страница 56: ...ed pump example 3 The operation of the pump will be controlled by the Master unit The Master Slave assembly is controlled on the water outlet without additional sensor Installation must only be carrie...

Страница 57: ...r water outlet temperature C 30RBM 160 400 and 30RBP 160 400 Low temperature Propylene Glycol Inlet air temperature C Brine solution water type heat exchanger water outlet temperature C NOTES Evaporat...

Страница 58: ...mmissioned by the manufacturer Glycol concentration required Ethylene and Propylene glycol freezing curve Glycol concentration 0 5 10 15 20 25 30 35 40 45 50 26 24 22 20 18 16 14 12 10 8 6 4 2 0 Ethyl...

Страница 59: ...an be configured in the Service Configuration menu Refer to the control manual The performances capacity efficiency noise level depend on the fan speed and the ductwork Please refer to the manufacture...

Страница 60: ...h fan V shaped air heat exchangers Top view Side view Detail of the duct connection interface frame Size of the duct connection frame 955x955x105mm 12 2 8 Duct installation principle Solution 1 each f...

Страница 61: ...ific to this option 12 2 9 Power factor correction Option 231 The power factor correction is active for all of the machine s operating conditions The power factor performance is guaranteed at 0 95 whe...

Страница 62: ...83 2240 2677 2695 2899 Unit with option 15 option 118A kg 1591 1613 2101 2137 2327 2384 2839 2857 3079 Unit with option 15 option 116S 118A kg 1730 1767 2261 2341 2530 2587 3081 3098 3359 30RBM 30RBP...

Страница 63: ...e various heat exchangers IMPORTANT During operation in Free Cooling mode the compressors are not used However depending on the operating conditions and the monitored pressure limits the system may be...

Страница 64: ...s control type fixed or variable speed please refer to the instructions in the Smart View control manual Following these parameters the Smart View control will activate the adequate number of digital...

Страница 65: ...erating weight 1 Standard unit kg 1580 1619 1620 1749 1750 Unit option 15 kg 1652 1686 1687 1841 1842 Unit option 15 option 116W kg 1818 1849 1850 2004 2020 Unit option 15 option 116W water buffer tan...

Страница 66: ...conditions 10K under Eurovent conditions 2 Maximum flow rate for a pressure drop of 100 kPa in the shell and tube exchanger 10 100 1 0 10 0 100 0 Pertes de charge kPa D bit l s 1 1 30RBM 30RBP 160 to...

Страница 67: ...ct Check for any general signs of deterioration Check the anti corrosion coatings 13 2 Level 2 maintenance This level requires specific expertise in electrical hydraulic and mechanical systems it is p...

Страница 68: ...itable for the products Any detected leaks must be repaired immediately The compressor oil that is recovered during maintenance contains refrigerant and must be treated accordingly Refrigerant under p...

Страница 69: ...NT Never use a pressure water spray without a large diffuser Concentrated and or rotating water jets are strictly forbidden Never use a fluid with a temperature above 45 C to clean the air heat exchan...

Страница 70: ...5 43 2490 67 4322 4 602 20 1344 44 2551 68 4416 3 626 21 1384 45 2614 69 4512 2 650 22 1425 46 2678 70 4610 1 674 23 1467 47 2744 0 700 24 1509 48 2810 1 726 26 1596 49 2878 2 752 25 1552 50 2947 3 77...

Страница 71: ...of the unit can be recycled for another purpose 14 3 Fluids to be recovered for treatment Refrigerant Heat transfer fluid depending on the installation water brine solution etc Compressor oil 14 4 Ma...

Страница 72: ...essories Preliminary equipment check Is there any shipping damage If so where Will this damage prevent unit start up Unit is level in its installation Power supply agrees with the unit nameplate Power...

Страница 73: ...included litres of Proper loop freeze protection included if required litres of Water pipes have been fitted with trace heating up to the evaporator Return water piping is equipped with a screen filt...

Страница 74: ...l checks are complete start up the unit The unit starts and operates properly Temperatures and pressures WARNING Once the unit has been operating for a while and the temperatures and pressures have st...

Страница 75: ......

Страница 76: ...alidity of certificate www eurovent certification com Order No 13539 05 2019 Supersedes order No 13539 12 2018 Manufactured by Carrier SCS Montluel France Manufacturer reserves the right to change any...

Отзывы: