12.2 - Description
12.2.1 - Hydraulic module without variable speed
(options 116R, 116S, 116T, 116U)
The hydraulic module is composed of the system's main
hydraulic components: factory-fitted water pump, screen filter
and relief valve.
The fixed speed operating pressure pump provides the nominal
flow rate for the system water loop.
Several types of water pump are available to suit all applications:
•
Single or dual low pressure pumps
•
Single or dual high pressure pumps.
The nominal flow rate of the system should be adjusted using
a manual control valve provided by the customer.
The relief valve placed on the water inlet pipes at the pump
inlet limits the pressure to 400 kPa (4 bar).
A screen filter that can be easily removed is placed at the pump
inlet and protects the pump and the plate heat exchanger against
solid particles that are greater than 1.2 mm.
Additional options can be ordered if necessary:
•
Protection of the hydraulic module in outdoor
temperatures of down to -20°C.
•
Expansion vessel.
The use of the hydraulic module on open systems is
prohibited.
12.2.2 - Hydraulic module with variable speed
(Options 116V, 116W)
The composition of the hydraulic module with variable speed
is similar to that of the hydraulic module without variable
speed.
In this case, the pump is controlled by a frequency inverter
that allows the pump's nominal flow to be adjusted based on
the chosen control mode (constant pressure or temperature
differential or fixed speed) and the installation's operating
conditions.
The use of the hydraulic module on open systems is
prohibited.
12.2.3 - Partial heat recovery (Option 49)
This option enables free hot water to be produced through
heat recovery by desuperheating the compressor outlet gas.
The option is available across the entire range.
A water-cooled heat exchanger is installed as standard with
air-cooled exchangers on the compressor discharge line on
each circuit.
The control is configured for the partial heat recovery option
in the factory (see the section on Control configuration with
the desuperheater option).
The installer must protect the water type heat exchanger
against the risk of frost.
12.2.3.1 - Physical properties of units with partial heat recovery using desuperheaters
30RBM/30RBP
160
180
200
220
260
300
330
360
400
430
470
520
Desuperheater in circuits A/B
Plate heat exchanger
Water volume circuits A/B
l
2/3,75 2/3,75 2/3,75 3,75/3,75 3,75/3,75 3,75/5,5 3,75/5,5 5,5/5,5 5,5/5,5 5,5/7,5 5,5/7,5 7,5/7,5
Maximum operating pressure, water side
kPa
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Refrigerant
Circuit A
(1)
kg
9,1
11,9
11,9
14,3
13,6
15,0
16,9
22,8
21,4
26,3
23,7
27,3
tCO
2
e
19,1
26,9
26,9
30,0
28,4
31,3
35,3
47,6
44,7
54,9
49,6
57,0
Circuit B
(1)
kg
13,5
14,3
13,3
14,5
13,6
22,8
21,1
20,9
22,4
27,4
27,3
27,5
tCO
2
e
28,1
30,0
27,7
30,2
28,4
47,6
44,1
43,7
46,8
57,1
57,1
57,4
Water connections
Victaulic
Connection
in
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
2"
External diameter
mm
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
60,3
30RBM
Operating weight
(1)
Standard unit + desuperheater option
kg
1258
1295
1296
1430
1452
1913
1949
2120
2178
2599
2616
2818
Unit with option 15 + desuperheater option
kg
1340
1378
1378
1538
1560
2039
2074
2264
2321
2761
2778
2998
Unit with option 15 and option 116S +
desuperheater option
kg
1480
1517
1518
1678
1714
2198
2279
2468
2525
3005
3022
3279
30RBP
Operating weight
(1)
Standard unit + desuperheater option
kg
1293
1332
1332
1467
1488
1950
1985
2157
2214
2656
2673
2884
Unit with option 15 + desuperheater option
kg
1376
1414
1415
1575
1596
2076
2111
2300
2358
2818
2835
3064
Unit with option 15 and option 116S +
desuperheater option
kg
1516
1554
1554
1714
1751
2235
2315
2505
2561
3063
3080
3345
*
Weights are guidelines only. Refer to the unit name plate.