22
For the high-pressure single and dual-pump motors of 30RBM/RBP 160-520 units (options 116R, 116S, 116V, 116W)
No.
(2)
Description
(3)
Units
30RBM/30RBP
160
180 200 220
260
300 330
360
400 430 470 520
1
Nominal efficiency at full load and nominal voltage
%
87,5 87,5 87,5 87,5 89,9 89,9
89
89
89
89,6 89,6 89,6
1
Nominal efficiency at 75% of full load and nominal voltage
%
88,2 88,2 88,2 88,2 90,4 90,4
90
90
90
90,8 90,8 90,8
1
Nominal efficiency at 50% of full load and nominal voltage
%
87,5 87,5 87,5 87,5 89,6 89,6 89,7 89,7 89,7 90,8 90,8 90,8
2
Efficiency level
-
IE3
3
Year of manufacture
-
This information varies depending on the manufacturer and model at the time of
incorporation. Please refer to the motor nameplates.
4
Manufacturer's name and trademark, commercial registration
number and manufacturer's head office
-
Same as above
5
Product's model number
-
Same as above
6
Number of motor poles
-
2
2
2
2
2
2
2
2
2
2
2
2
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
kW
3
3
3
3
4
4
5,5
5,5
5,5
7,5
7,5
7,5
7-2
Maximum input power (400 V)
(4)
kW
3,81 3,81 3,81 3,81 4,96 4,96 6,80 6,80 6,80 9,16 9,16 9,16
8
Rated input frequency
Hz
50
50
50
50
50
50
50
50
50
50
50
50
9-1
Nominal voltage
V
3 X 400
9-2
Maximum current drawn (400 V)
(5)
A
6,81 6,81 6,81 6,81 8,27 8,27 11,30 11,30 11,30 15,30 15,30 15,30
10
Nominal speed
rps - rpm
48 - 2900
11
Product disassembly, recycling or disposal at end of life
-
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
12
Operating conditions for which the motor is specifically designed
I- Altitudes above sea level
m
< 1000
(6)
II - Ambient air temperature
°C
< 40
III - Maximum operating temperature
°C
Please refer to the operating conditions given in this manual or
in the specific conditions given in the Carrier selection programs.
V - Potentially explosive atmospheres
-
Non ATEX environment
(1) Required by regulation No. 640/2009 concerning the application of directive 2009/125/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(5) To obtain the maximum operating current draw for a unit with hydraulic module, add the maximum unit current draw from the electrical data table to the pump current draw.
(6) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
5.7 - Electrical data notes for the compressors
Cp
I Nom
I Max
Un
I Max
Un-10 %
LRA
Un
Cosinus
Phi Max
00PSG001961100A
30
41
44
215
0,89
00PSG001748000A
37
50
54
260
0,89
Cp
Compressor
I Nom
Nominal current draw (A) at standardised Eurovent equivalent conditions (see definition of conditions under nominal unit current draw)
I Max
Maximum operating current (A)
LRA
Locked rotor current (A)
Cos phi Max @I Max
5.8 - Distribution of compressors per circuit
Cp
Circuit
160
180
200
220
260
300
330
360
400
430
470
520
00PSG001961100A
A
1
-
-
2
-
-
-
3
-
3
-
-
B
2
2
-
2
-
3
-
-
-
-
-
-
00PSG001748000A
A
-
1
1
-
2
2
2
-
3
-
3
4
B
-
-
2
-
2
-
3
3
3
4
4
4
Cp
Compressor
I Nom
Nominal current draw (A) at standardised Eurovent equivalent conditions (see definition of conditions under nominal unit current draw)
I Max
Maximum operating current (A)
LRA
Locked rotor current (A)
Cos phi Max @I Max
Содержание 30RBM 160
Страница 75: ......