70
13.10 - Refrigerant properties
Properties of R410A
Saturated temperatures (°C) based on the relative pressure (in kPa)
Satur. temp.
Relative pressure
Satur. temp.
Relative pressure
Satur. temp.
Relative pressure
Satur. temp.
Relative pressure
-20
297
4
807
28
1687
52
3088
-19
312
5
835
29
1734
53
3161
-18
328
6
864
30
1781
54
3234
-17
345
7
894
31
1830
55
3310
-16
361
8
924
32
1880
56
3386
-15
379
9
956
33
1930
57
3464
-14
397
10
987
34
1981
58
3543
-13
415
11
1020
35
2034
59
3624
-12
434
12
1053
36
2087
60
3706
-11
453
13
1087
37
2142
61
3789
-10
473
14
1121
38
2197
62
3874
-9
493
15
1156
39
2253
63
3961
-8
514
16
1192
40
2311
64
4049
-7
535
17
1229
41
2369
65
4138
-6
557
18
1267
42
2429
66
4229
-5
579
19
1305
43
2490
67
4322
-4
602
20
1344
44
2551
68
4416
-3
626
21
1384
45
2614
69
4512
-2
650
22
1425
46
2678
70
4610
-1
674
23
1467
47
2744
0
700
24
1509
48
2810
1
726
26
1596
49
2878
2
752
25
1552
50
2947
3
779
27
1641
51
3017
13.11 - Power factor correction
The check involves measuring the input current of each capacitor battery. The check must be carried out using a true RMS
meter reading:
Check per phase current delivered by each capacitor and compare it to nominal values. In case of capacitance losses or
unbalance, the capacitors must be replaced.
Make sure the current through the capacitor does not exceed 1.3 x Ir. A higher value may indicate a strong presence of
harmonics, which will impact the lifetime of the capacitor.
The absence of current despite the capacitor being energized indicates a fault. This defect is confirmed by removing the
capacitors and checking the underside.
Faulty
Correct
Содержание 30RBM 160
Страница 75: ......