“optiMist” +0300065EN - rel. 1.6 - 18/06/2021
Message displayed
Cause
Solution
Reset
Alarm
status
Action
symbol
Notes
Clock fault alarm
backup battery completely
discharged or general clock
fault
replace/repair electronic
controller
Note*
not active Stop production
off
* switch the unit off to
repair or replace the
electronic controller
Temperature bypass
probe faulty or
disconnected alarm
bypass temperature probe
disconnected or broken
check connection and
operation of the probe
manual
active
Stop production
on
High humidity alarm
(Humidification)
value measured by the main
probe is greater than the
humidity alarm threshold
check the parameter setting
manual
not active signal only
on
Low humidity alarm
(Humidification)
value measured by the
main probe is less than the
humidity alarm threshold
check the parameter setting
manual
not active signal only
on
Limit probe high
humidity alarm
(Humidification)
value measured by the limit
probe is greater than the
humidity alarm threshold
check the parameter setting
manual
not active signal only
on
* Active only if limit
probe is present and set
to humidity
High temperature
main probe (IEC)
alarm
value measured by the main
probe is greater than the
humidity alarm threshold
check the parameter setting
manual
not active signal only
on
Low temperature
main probe (IEC)
alarm
value measured by the
main probe is less than the
humidity alarm threshold
check the parameter setting
manual
not active signal only
on
High humidity/
temperature limit
alarm (IEC)
value measured by the limit
probe is greater than the
humidity alarm threshold
check the parameter setting
manual
not active signal only
on
* Active only if limit
probe is present and set
to humidity
Rack capacity not set
alarm
Wizard did not complete
correctly. One or more rack
capacities are set to zero.
check the parameter set by the
Wizard or the Installer menu
automatic active
Stop production
on
* not visible during the
Wizard
Alarms: Heat
recovery activation
from analog input
signal broken or
disconnected
Value outside of range
(generally -9999 or +9999)
Check electrical connection
manual
not active Stop production *
on
* only IEC production
Low rack temperature The temperature measured on
the rack is lower than the set
threshold
Check the environmental
conditions near the rack, or set
a higher threshold
Manual
Active
Display only
on
If reduction in
production due to low
rack temperature is
enabled (screen Bbc05),
current production is
reduced based on the
measured temperature
Tab. 9.a