“optiMist” +0300065EN - rel. 1.6 - 18/06/2021
Rotation function
The rotation function allows the periodical activation of the two cabins.
In the main cabin:
• enable Rotation function,without enabling the backup;
• set the Rotation time value.
In the backup cabin the HBT control must be set.
To permit the rotation to work, the wiring of the HBT control must be
done from the main cabin to the backup one and vice versa.
3.13 Supervisor network
J5
J4
J3
J2
J1
serial card
field card
service card
ID1
ID2
ID3
ID4
ID5
ID7
ID8
IDC1
VG
VG
0
Y1
Y2
Y3
Y4
B4
BC4
B5
BC5
B1
B2
B3
J24
+V
term
GND
+5V
ref
GND
+VDC
G
G0
NO8
C7
C4
C1
C8
NO7
NO4
NO1
NC8
C7
NO5
NO2
NO3
C4
C1
Rx-/Tx-
Rx+/Tx+
GND
J9
J10
J11
J12
J13
J14
J15
input: 24 V / V ; 50 to 60 Hz
max. power: 40 VA / 15 W
J3
J2
field card
ID1
ID2
ID3
ID4
ID5
ID7
ID8
IDC1
VG
VG
0
Y1
Y2
Y3
Y4
B4
BC4
B5
BC5
B3
GND
+VDC
ID7
ID7
ID5
ID5
ID4
ID4
ID3
ID3
ID2
ID2
ID1
ID1
Y4
Y4
Y3
Y3
Y2
Y2
Y1
Y1
VG
0
VG
0
VG
VG
Fig. 3.aa
Optional CAREL cards
network/card
protocol supported
PCOS004850
RS485
CAREL, Modbus®
PCO100MDM0 RS232 (external modem) CAREL for remote connections
PCO1000WB0 Ethernet™
TCP/IP
SNMP v1 &v2c
BACnet™ Ethernet™ ISO8802-2/8802-3
BACnet/IP
PCO1000BA0
Ethernet™ (Modbus®)
BACnet™ MS/TP
Tab. 3.d
Important:
Follow the instructions shown on the optional cards
for the technical specifi cations, connections and expansion boards.
Default: CAREL supervisor protocol.
3.14 Supervisory optiMist Table
Type
Carel
Index
Modbus
®
Index
Name
Description
R/W
Min
Limit
Max
limit
Def.
Unit of
measure
Alarms
1
1
Al_No_Model
Alarm: model not yet confi gured
R
0
1
2
2
Al_Setting_Nominal_MFR
Alarm: capacity of the distribuition system not yet confi gured
R
0
1
3
3
Al_RO_Not_Ready
Alarm: Water Treatement System
R
0
1
4
4
mAl_LP_Detected_New
Alarm: Low Pressure by pressostat (ID5)
R
0
1
5
5
Al_high_Temp_Bypass
Alarm: High temperature water in bypass
R
0
1
6
6
Al_VFD_Not_Ready
Alarm: Inverter
R
0
1
8
8
Al_Antifreeze_Temp
Alarm: low temperature in cabinet
R
0
1
9
9
Al_HP_Detected
Alarm: drop separator clogged
R
0
1
10
10
mAl_High_Press
Allarme: alta pressione da sonda
R
0
1
11
11
mAl_LP_Probe
Alarm: low pressure by probe
R
0
1
12
12
mAl_Probe8_Broken
Alarm: pressure probe broken or unconnected
R
0
1
13
13
mAl_Probe1_Broken
Alarm: I.E.C. - main probe broken or unconnected
R
0
1
14
14
mAl_Probe2_Broken
Alarm: I.E.C. - limit probe broken or unconnected
R
0
1
15
15
mAl_Probe6_Broken
Alarm: I.E.C. - main probe broken or unconnected
R
0
1
16
16
mAl_Probe7_Broken
Alarm: I.E.C. - limit probe broken or unconnected
R
0
1
17
17
mAl_Probe5_Broken
Alarm: AUX probe broken or unconnected
R
0
1
18
18
Clock_Error
Error reading/writing the RTC (real time clock) data and/or clock RAM
R
0
1
19
19
mAl_Probe4_Broken
Alarm: water temperature probe broken or unconnectd
R
0
1
20
20
Al_High_humid
Alarm: HUMIDIFICATION high humidity
R
0
1
21
21
Al_Low_Humid
Alarm: HUMIDIFICATION low humidity
R
0
1
22
22
Al_Limit_Humid
Alarm: HUMIDIFICATION high limit temperature/humidity
R
0
1
23
23
Al_High_Temp_EC
Alarm: I.E.C. high limit temperature
R
0
1
24
24
Al_Limit_Humid_EC
Alarm: I.E.C. high limit temperature/humidity
R
0
1
25
25
mAl_Probe3_Broken
Alarm: I.E.C. heat recovery activation signal by analog input broken or
unconnected
R
0
1
26
26
Al_warn_RO
Warning: Water Treatment System
R
0
1
Analg.
1
1
View_Value
HUMID: main/regulation probe [B1]
R
-20,0
-4,0
0
0
70,0
158,0
100,0
100,0
°C /°F / %rH
/ %
2
2
View_Value_Lim
HUMID:: limit probe [B2]
R
-20,0
-4,0
0
1
70,0
158,0
100,0
100,0
°C /°F / %rH
/ %
3
3
View_Value_EC
I.E.C.: main/regulation probe [B6]
R
-20,0
-4,0
0
2
70,0
158,0
100,0
100,0
°C /°F / %rH
/ %