20
ENG
“optiMist” +0300065EN - rel. 1.6 - 18/06/2021
Analg.
4
4
View_Value_Lim_EC
I.E.C.: limit probe [B7]
R
-20,0
-4,0
0
3
70,0
158,0
100,0
100,0
°C /°F / %rH
/ %
5
5
Probe3_Value
I.E.C.; Heating recovery activation analog signal [B3]
R
0
100,0
%
6
6
T_Probe_View
Water temperature [B4]
R
-20,0
-4,0
70,0
158,0
°C/°F
7
7
View_Value_AUX
AUX probe temperature [B5]
R
-20,0
-4,0
70,0
158,0
°C/°F
8
8
P_Probe_View
Pressure of outlet water [B8]
R
0
20,0 /300
bar/psi
9
9
Setp_Humid
HUMID: Main regulation humidity sepoint
R/W
0
100,0
50,0
%rH
10
10
Humid_Diff
HUMID: Main regulation humidity delta
R/W
0
100,0
5,0
%rH
11
11
L_Humid_Set
HUMID.: Limit probe humidity sepoint [%rH]
R/W
0
100,0
100,0
%rH
12
12
L_Humid_Diff
Humid: Limit probe humidity delta [%rH]
R/W
0
100,0
5,0
%rH
13
13
L_Temp_Set
Humid.: Limit probe temperature sepoint
R/W
0
100,0
25,0
77,0
°C/°F
14
14
L_Temp_Diff
Humid: Limit probe temperature delta
R/W
0
100,0
5,0
41
°C/°F
15
15
Main_Prb_Setpoint_EC
I.E.C.: Main regulation temperature sepoint
R/W
0
99,9
25,0/77,0
°C/°F
16
16
Main_Prb_Delta_EC
I.E.C.: Main regulation temperature delta
R/W
0
99,9
2,0 / 35
°C/°F
17
17
Main_Prb_Band_EC
I.E.C.: Main regulation temperature band
R/W
0
99,9
5,0 / 41
°C/°F
18
18
Limit_Prb_Setp_HF_EC
I.E.C.: Limit probe humidity sepoint
R/W
0
100,0
95,0
%rH
19
19
Limit_Prb_Band_HF_ECHF
I.E.C.: Limit probe humidity delta
R/W
0
100,0
5,0
%rH
20
20
Limit_Prb_Setp_T_EC
I.E.C.: Limit probe temperature sepoint
R/W
0
99,9
20,0 / 68
°C/°F
21
21
Limit_Prb_Band_T_ECHF
I.E.C.: Limit probe temperature delta
R/W
0
99,9
5,0 / 41
°C/°F
22
22
High_Room_Humid
HUMID: threshold high humidity by main regulation probe reading
R/W
0
100,0
100,0
%rH
23
23
Low_Room_Humid
HUMID: threshold low humidity by main regulation probe reading
R/W
0
100,0
0
%rH
24
24
High_Limit_Humid
HUMID. threshold high humidity by limit probe reading
R/W
0
100,0
100,0
%rH
25
25
High_Limit_Temp
HUMID: threshold high temperature by limit probe reading
R/W
0
150,0
40,0/104
°C/°F
26
26
High_Room_Temp_EC
I.E.C.: threshold high temperature by main regulation probe reading
R/W
0
150,0
40,0/104
°C/°F
27
27
Low_Room_Temp_EC
I.E.C.: threshold low temperature by main regulation probe reading
R/W
0
150,0
10,0 / 50
°C/°F
28
28
High_Limit_Humid_EC
I.E.C.: threshold high humidity by limit probe reading
R/W
0
100,0
100,0
%rH
29
29
High_Limit_Temp_EC
I.E.C.: threshold high temperature by limit probe reading
R/W
0
150,0
40,0/104
°C/°F
Dig.
41
41
Unit_Measure
Unit measure (0=International System; 1= Imperial)
R/W
0
1
42
42
Type_Machine_208
Supply voltage (0= 230V 50Hz; 1=230V 60Hz)
R
0
1
43
43
Priority_Humidity_Running
Zone running (0=I.E.C., 1= Humidification)
R
0
1
44
44
Priority_Humidity_Din
Priority summer/winter mode by digital input (0=I.E.C., 1=Humidification)
R
0
1
45
45
Heat_Recovery_Active
I.E.C.: heat recovery status (0=Not active; 1=Active)
R/W
0
1
46
46
Lim_Flow_EC_Type
I.E.C.: Flow limit signal type( 0=Damper; 1=Fan)
R
0
1
47
47
Dout_02
Pump activation status [Dout 02]
R
0
1
48
48
Dout_10
Water treatment system status [Dout 10]
R
0
1
49
49
Dout_01
Main line fill valve status (0=closed; 1=opened) [Dout 1]
R
0
1
50
50
Dout_04
Step 1 fill valve status (0=closed; 1=opened) [Dout 4]
R
0
1
51
51
Dout_05
p 2 fill valve status (0=closed; 1=opened) [Dout 5]
R
0
1
52
52
Dout_06
Step 1 drain valve status (0=closed; 1=opened) [Dout 6]
R
0
1
53
53
Dout_09
Step 2 drain valve status (0=closed; 1=opened) [Dout 9]
R
0
1
54
54
Dout_03
Main line drain valve status (0=closed; 1=opened) [Dout 3]
R
0
1
55
55
Req_Wash
Request of wash procedure running
R
0
1
56
56
Dout_13
Anti-freeze procedure activation[Dout 13]
R
0
1
57
57
Dout_12
Heartbeat of this cabinet [Dout 12]
R
0
1
58
58
Heartbeat_Din
BACKUP: Other cabinet heartbeat by digital input [ID 4]
R
0
1
59
59
Superv_OnOff
On/Off by supervisor (0=Off, 1=On)
R/W
0
1
60
60
En_Scheduler
Enable time scheduler
R/W
0
1
0
61
61
En_Reg_From_Superv
HUMIDIFICATION: enable regulation by supervisor
R/W
0
1
0
62
62
En_Reg_EC_From_Superv
I.E.C.: enable regulation by supervisor
R/W
0
1
0
63
63
Heat_Recovery_Active_BMS Enable heat recovery by supervisor
R/W
0
1
0
64
64
En_Defrost
Enable anti-freeze function
R/W
0
1
0
65
65
RESET_ALARMS
Request to reset/clear alarm memories
R/W
0
1
0
66
66
SET_DAY
Request to copy NEW_DAY into DAY
R/W
0
1
0
67
67
SET_MONTH
Request to copy NEW_MONTH into MONTH
R/W
0
1
0
68
68
SET_YEAR
Request to copy NEW_YEAR into YEAR
R/W
0
1
0
69
69
SET_HOUR
Request to copy NEW_HOUR into HOUR
R/W
0
1
0
70
70
SET_MINUTE
Request to copy NEW_MINUTE into MINUTE
R/W
0
1
0
71
71
Remote_Hum_Req
HUMIDIFICATION: request by on/off contact
R
0
1
72
72
Remote_EC_Req
I.E.C.: request by on/off contact
R
0
1
73
73
Air_Flow_Switch
Flux digital input status [ID 9]
R
0
1
74
74
Aux_Enabled
Enable AUX probe [B5]
R/W
0
1
75
75
HeartBeat_Superv
BACKUP: heart heartbeat other cabinet (by supervisor)
R/W
0
1
76
76
En_rotation
Enable rotation between two cabinets
R/W
0
1
87
87
Default_Ahead
Memory erasing and default values intallation running
R
0
1
90
90
Heart_Beat_RC2
Test pCO (write 1, after 2 s this variable is reset)
R/W
0
1
Int.
1
209
Type_Machine_Display
Model of the cabinet
R
1
13
2
210
Qa_N_Pump_Display
Pump capacity
R
0
1000
2200
kg/h / lb/h
3
211
N_Steps
Number of steps present
R
1
2
4
212
Qa_N_Rack_X
HUMIDIFICATION: steps capacity
R
0
1000
2200
5
213
Qa_N_Rack_2_X
I.E.C.: steps capacity
R
0
1000
2200
6
214
Installation_Type
Installation type ( 0=I.E.C., 1=Humidification, 2= Humidifi I.E.C. )
R
0
2
7
215
Unit_Status
Main mask status visualization (0=OFF BY SCHEDULER;1=REMOTE
OFF;2=OFF BY KEYBOARD;3=OFF BY SUPERVISOR;4=OFF BY
FLUXOSTAT;5=PUMP OFF BY KEYBOARD.;6=PUMP OFF BY REMOTE.;7=PRE
SSURIZATION;8=WATER INLET WAITING;9=OFF BACKUP;10=ALARM;11=W
ARNING;12=not used...;13=TEST PRESS. IN;14=FILLING;15=WASHING;16=R
EADY;17=PRODUCTION;18=BYPASS CALIBRATION;19=INIZIALIZATION;)
R
0
19
8
216
Main_Status
Main status
R
0
25
9
217
Qr_Pump
0-10V signal to inverter (0-1000) [Aout Y2]
R
0
1000
10
218
Regulation_Type
HUMIDIFICATION: Regulation type 0=Reg.Humidity, 1=Reg.hum.+Limit
Humid., 2=Reg.Humid+Limit Temp, 3=Not used, 4=Not used, 5=Not used,
6=External prop.signal., 7=Ext.limit Humid, 8=Ext.limit
Temp,9=ON/OFF ext.contact
R
0
9
11
219
Humidity_Cfg
HUMIDIFICATION: Main probe type ( 0=NTC;1=0-1 V; 2=2-10 V;3= 0-10 V;
4=0-20 mA; 5=4-20 mA; 6=0-135 ohm; 7=135-1k ohm )
R
0
7
12
220
Limit_Cfg
HUMIDIFICATION: Limit probe type ( 0=NTC;1=0-1 V; 2=2-10 V;3= 0-10 V;
4=0-20 mA; 5=4-20 mA; 6=0-135 ohm; 7=135-1k ohm )
R
0
7