Register
(Decimal)
Register
(Hex)
Description
Data
Type
Units
Access
9857
2681
Slave Device 15: Flow Run Config: Gas Fraction
FP
—
RW
9858
2682
Slave Device 15: Flow Run Config: Plate Diameter
FP
inch
RW
9859
2683
Slave Device 15: Flow Run Config: Pipe Diameter
FP
inch
RW
9860
2684
Slave Device 15: Flow Run Config: Cone Beta
FP
—
RW
9861
2685
Slave Device 15: Flow Run Config: Nominal Value
FP
—
RW
9862
2686
Slave Device 15: TFM Config: T1 Nominal Factor
FP
pulses/gal
RW
9863
2687
Slave Device 15: TFM Config: T2 Nominal Factor
FP
pulses/gal
RW
Slave 16 Configuration (Floating Points)
Register
(Decimal)
Register
(Hex)
Description
Data
Type
Units
Access
9876
2694
Slave Device 16: Flow Run Config: Atmospheric
Pressure
FP
psia
RW
9877
2695
Slave Device 16: Flow Run Config: Carbon Dioxide
FP
—
RW
9878
2696
Slave Device 16: Flow Run Config: Nitrogen
FP
—
RW
9879
2697
Slave Device 16: Flow Run Config: Specific Gravity
FP
—
RW
9880
2698
Slave Device 16: Flow Run Config: Heating Value
FP
MMBtu/ft³
RW
9881
2699
Slave Device 16: Flow Run Config: Oil Density
FP
lbm/ft³
RW
9882
269A
Slave Device 16: Flow Run Config: Gas Fraction
FP
—
RW
9883
269B
Slave Device 16: Flow Run Config: Plate Diameter
FP
inch
RW
9884
269C
Slave Device 16: Flow Run Config: Pipe Diameter
FP
inch
RW
9885
269D
Slave Device 16: Flow Run Config: Cone Beta
FP
—
RW
9886
269E
Slave Device 16: Flow Run Config: Nominal Value
FP
—
RW
9887
269F
Slave Device 16: TFM Config: T1 Nominal Factor
FP
pulses/gal
RW
9888
26A0
Slave Device 16: TFM Config: T2 Nominal Factor
FP
pulses/gal
RW
Slave 17 Configuration (Floating Points)
Register
(Decimal)
Register
(Hex)
Description
Data
Type
Units
Access
9901
26AD
Slave Device 17: Flow Run Config: Atmospheric
Pressure
FP
psia
RW
9902
26AE
Slave Device 17: Flow Run Config: Carbon Dioxide
FP
—
RW
9903
26AF
Slave Device 17: Flow Run Config: Nitrogen
FP
—
RW
9904
26B0
Slave Device 17: Flow Run Config: Specific Gravity
FP
—
RW
9905
26B1
Slave Device 17: Flow Run Config: Heating Value
FP
MMBtu/ft³
RW
9906
26B2
Slave Device 17: Flow Run Config: Oil Density
FP
lbm/ft³
RW
9907
26B3
Slave Device 17: Flow Run Config: Gas Fraction
FP
—
RW
9908
26B4
Slave Device 17: Flow Run Config: Plate Diameter
FP
inch
RW
9909
26B5
Slave Device 17: Flow Run Config: Pipe Diameter
FP
inch
RW
9910
26B6
Slave Device 17: Flow Run Config: Cone Beta
FP
—
RW
86
Section 1
Scanner 3100 Modbus Protocol
Содержание Scanner 3100
Страница 1: ...Scanner 3100 Modbus Protocol Manual Manual No 50280809 Rev 04 ...
Страница 192: ...This page is left blank intentionally 192 Section 2 Scanner 3100 Modbus Protocol ...
Страница 196: ...This page is left blank intentionally A 4 Appendix A Scanner 3100 Modbus Protocol ...
Страница 198: ......