Register
(Decimal)
Register
(Hex)
Description
Data
Type
Units
Access
5226
146A
Analog Output 1 PID: Holding: Override Enable
INT32
—
RO
5227
146B
Analog Output 2 PID: Holding: Override Enable
INT32
—
RO
Digital Output Status
Digital Output: Holding: Output
Digital Output: Holding: Output registers report the state of the corresponding digital output when Digital Input/Output
mode is configured as one of the following settings:
•
Alarm.
Selected device alarms.
•
Conditional.
Value above setpoint, value below setpoint, or value out of setpoint range.
•
Programmed
.
Time of day output control or controlled output state (via serial port).
Read the corresponding register to determine its output state.
Value
Output Status
0
Disabled
1
Enabled
Digital Output: Holding: Pulses
Digital Output: Holding: Pulses registers can be used to set the Digital Output state when the Digital Input/Output mode
is configured as “Programmed–Controlled Output State (via serial port).”
Value
Output Status
0
Disabled
Any other integer
Enabled
Write a value to the desired Digital Output: Holding: Pulses register to set the output state. Read the corresponding Hold-
ing: Output register to validate the digital output status.
Flow Run 1 Holding (Integers)
Register
(Decimal)
Register
(Hex)
Description
Data
Type
Units
Access
5301
14B5
Flow Run 1: Configure: Calculation Period
INT32
—
RW
5302
14B6
Flow Run 1: Configure: Fluid Calculation Interval
INT32
—
RW
5303
14B7
Flow Run 1: Configure: Dampening Mode
INT32
—
RW
5304
14B8
Flow Run 1: HAccum: Flow Direction
INT32
—
RO
5305
14B9
Flow Run 1: HFluid: Method
INT32
—
RO
5306
14BA
Flow Run 1: HFluid: Override
INT32
—
RO
5307
14BB
Flow Run 1: HFlow: Method
INT32
—
RO
5308
14BC
Flow Run 1: HFlow: Override
INT32
—
RO
5309
14BD
Flow Run 1: HFlow: Installation Parameters
INT32
—
RO
5310
14BE
Flow Run 1: HFlow: Meter Tube Material
INT32
—
RO
5311
14BF
Flow Run 1: HFlow: Orifice Material
INT32
—
RO
28
Section 1
Scanner 3100 Modbus Protocol
Содержание Scanner 3100
Страница 1: ...Scanner 3100 Modbus Protocol Manual Manual No 50280809 Rev 04 ...
Страница 192: ...This page is left blank intentionally 192 Section 2 Scanner 3100 Modbus Protocol ...
Страница 196: ...This page is left blank intentionally A 4 Appendix A Scanner 3100 Modbus Protocol ...
Страница 198: ......