Code
Description
Arg
1
Arg
2
Arg
3
Arg
4
Config
Lock
If Config Lock = Yes, an active configuration lock in the Scanner prevents changes to the register.
600300 Stores the current
Flow Run Factor
Calibration Map Data
as a new calibration.
Web interface should
be used to configure
the calibration type.
New factors must be
written (per the Linear
Calibration Factor
procedure below)
before sending this
command.
1 = Flow Run 1
2 = Flow Run 2
—
—
—
Yes
600302 Stores the current
Input K-Factor
Calibration Map Data
as a new calibration.
Web interface should
be used to configure
the calibration type.
New factors must be
written (per the Linear
Calibration Factor
procedure below)
before sending this
command.
1 = Pulse Input 1
2 = Pulse Input 2
3 = Pulse Input 3
—
—
—
Yes
601000 Programs the
operating mode for
a PID controller. The
analog output must
be in PID mode for
this command to take
effect.
1 = Analog Output 1
2 = Analog Output 2
0 = Automatic
1 = Manual Override
—
—
No
601001 Changes the
operating mode for
a PID Controller to
manual and sets an
override value. The
target analog output
must be in PID mode
for this command to
take effect.
1 = Analog Output 1
2 = Analog Output 2
Override: 0.0 to 1.0
written as 32-bit
floating point.
For example: To
apply a 0.75 override,
convert 0.75 to a
32-bit floating point
(0x3F400000),
write the value to
Argument 2, and write
command.
—
—
No
121
Scanner 3100 Modbus Protocol
Section 2