Boiler inspection and maintenance
16
57
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
16.9 Troubleshooting the GC124 SP
Equipment required: Wiring diagrams (
Î
Chapter 19, page 80) and voltage detectors for 120 VAC and 24 VAC.
•
Verbindungen zur Gasarmatur prüfen.
•
Geht die Zündflamme aus, prüfen, ob das Thermoelement dicht mit den
Gasventilen abschließt; wenn ja Thermoelement austauschen.
•
Geht die Zündflamme immer wieder aus, Gasventile austauschen.
•
Prüfen, ob alle handbetätigten Gasabsperrventile geöffnet, Gasan-
schlüsse und Druckmesswerte in Ordnung und Zündgasdüsen nicht ver-
stopft sind.
•
Check connections to gas valve.
•
If the ignition flame goes out, check that the thermocouple is firmly
screwed to the gas valve; if yes, replace thermocouple.
•
If the ignition flame continues to go out, replace gas valve.
•
Check that all manually operated gas shut-offs are open; check that gas
connections and pressures are correct and that pilot orifice is not blocked.
Start
Set gas valve ON/OFF knob
clockwise to OFF position.
Close main gas shut-off. Set
thermostat (control) to heat re-
quirement (vent damper
opens).
Switch on power.
Set gas valve ON/OFF knob
counterclockwise to PILOT posi-
tion. Open main gas shut-off.
Press red pilot ignition button
and ignite ignition flame. Hold
down red pilot ignition button for
one minute and then release. Ig-
nition flame is burning.
•
Check electrical power source, low-voltage transformer, thermostat (con-
trol) and wiring. Check that the vent damper is open and the limit switch
is present.
No
No
No
Set gas valve ON/OFF knob
counterclockwise to ON. Main
burner ignites.
•
Check 24-V voltage at the gas valve.
•
Check electrical connections to gas valve. If OK replace gas valve.
No
System operates until the heat
requirement ends.
•
Check that the ignition flame surrounds the thermocouple and burns
evenly with a bluish flame. If OK replace thermocouple.
No
Heat requirement ended, sys-
tem switches off, vent damper
closes. Ignition flame continues
to burn.
•
Check operation of thermostat (control).
•
Disconnect 24-V connection to gas valve. If gas valve closes, check ther-
mostat and electrical wiring again.
•
If the gas valve does not close, replace gas valve.
End of troubleshooting
Repeat procedure until heating system operates properly.