Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Final start-up procedures for GC124 II models
12
Checking aquastat
Check the function of the maximum aquastat to make
sure that it switches the boiler off as soon as the boiler
water temperature set at the aquastat is reached.
Record the result in the start-up protocol.
25.
Set aquastat to its desired setting.
26.
Replace front door and close.
Fig. 28
Checking aquastat
1
Adjustment knob
1