Boiler inspection and maintenance
16
Performing final checks
14.
Place boiler in operation as directed in
Î
Chapter 11, page 26 to page 29.
15. For GC124 II:
Follow instructions in
Î
Chapter 12,
page 30 to page 34.
16. For GC124 SP:
Follow instructions in
Î
Chapter 13,
page 35 bis page 39.
17.
Test low water alarm if installed.
18.
Check area around boiler for hazards.
Complete the maintenance protocol to confirm that all
maintenace work has been conducted. Sign the mainte-
nance protocol and discuss it with the owner of the heat-
ing system.
WARNING!
RISK OF FIRE
From flammable material or liquids.
z
The area around the boiler must be free
from flammable substances, gasoline
or any other flammable or corrosive va-
pors and liquids.
z
Maintain a minimum distance of
15 inches around the boiler.
WARNING!
RISK TO LIFE
from explosion of flammable gases.
z
After maintenance work leaks can oc-
cur in pipes and threaded fastenings.
z
Make a thorough check for leaks.
z
Use only approved leak testing agents
to search for leaks.