Boiler inspection and maintenance
16
45
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
16.5 Cleaning the boiler
The boiler can be cleaned with brushes and/or by wet
cleaning. Cleaning tools are available as accessories.
Inspecting the ignition burner of the GC124 II
1.
Observe the ignition burner through the sight glas
(
Î
Fig. 39).
2.
The flame must rise over the sensor by ½" to 1-½".
3.
The pilot ignition gas pressure must be adjusted if
the flame is too small or too large.
Fig. 39
GC124 II boiler
1
Sight glass
1
Fig. 40
Correct ignition flame setting
1
Flame rises ½" to 1-½" above sensor
2
Ignition flame
1
2
USER NOTE
The adjustment screw is located behind a
safety screw on the gas valve (
Î
Fig. 41,
page 46).