Installation and maintenance instructions Gas Boiler Logano GC124 II/SP • Issue 07/2006
We reserve the right to make any changes due to technical modifications.
Final start-up procedures for GC124 II models
12
12 Final start-up procedures for GC124 II models
Verifying the ignition spark
1.
Look through the sight glass at the igniter and verify
that a spark is visible.
2.
Should no spark be visible continue to
troubleshooting in
Î
Chapter 16.8, page 55.
3.
Turn ON/OFF knob (
Î
Fig. 23) counterclockwise to
the ON position.
4.
The ignition flame will appear and ignite the main
burner. If the main burner does not ignite, close the
gas shut-off. Disconnect heating system from the
power source and inform your customer service
technician or gas company.
Fig. 22
GC124 II boile
1
Sight glass
1
Fig. 23
GC124 II gas valve
1
ON/OFF knob (shown in ON position)
1
WARNING!
RISK TO LIFE
from fire or explosion.
z
Never use excessive force on the
ON/OFF knob (
Î
Fig. 23).
z
Turn ON/OFF knob only by hand.
z
Never use tools to turn knob.
z
If you are unable to turn the knob by
hand, do not try to repair it.
z
Call Buderus technical service for
assistance.